61
www.kistlermorse.com
97-1129-01 Rev. D
75 DSP Factor
Determines the magnitude of change from the old reference median to the new reference
median, for change triggered by the DSP Qualify parameter. In example 2 in Figure 13,
the SVS2000 moves the reference median 80% of the distance from the old median to
the last weight (which triggered the change), based on a DSP Factor of 80%. A value of
100% sets the new median to the last weight value; a value of 50% sets the new median
halfway between the old median and the last weight value. note that DSP Factor does not
affect the change caused by a signal falling outside of the DSP Step window, as shown in
example 1 in Figure 13. The default for DSP Factor is 100%.
Figure 13. DSP Filter Parameters
SeTTIng up The dSp FIlTer
Follow this procedure to set up the DSP Filter:
1. If the SVS2000 is in Run Mode, press the ‘7’ Key, ‘2’ Key, and Enter Key to access the menu tree. The
display shows:
72 DSP enABLe
2. Press the enter key to access this menu. The display looks like this:
DSP FILTer *On
(Asterisk indicates the current selection.)
If the displayed menu does not show DSP Filter On, press the Up Arrow Key to display the next page of
the menu.
3. When the display shows DSP Filter On, press the Enter Key. The display acknowledges the selection and
returns to:
72 DSP enABLe
4. Press the up Arrow key to proceed to the next menu. The display shows:
73 DSP STEP
5. Press the enter key to access the DSP Step menu. The display looks like this:
> 400 lbs
Содержание SVS2000
Страница 1: ...SVS2000 Installation Operation Manual IOM97 1129 01 Rev D...
Страница 2: ......
Страница 10: ...6 97 1129 01 Rev D www kistlermorse com...
Страница 11: ...7 www kistlermorse com 97 1129 01 Rev D...
Страница 12: ...8 97 1129 01 Rev D www kistlermorse com...
Страница 13: ...9 www kistlermorse com 97 1129 01 Rev D...
Страница 14: ...10 97 1129 01 Rev D www kistlermorse com...
Страница 20: ...16 97 1129 01 Rev D www kistlermorse com Figure 3 Wiring Diagram Current Output Card venture...