Chapter 2: Installation
KFP-AF Series Installation Manual
21
Connecting the batteries
The control panel requires two 12 V, 7.2, 12, or 18 Ah rechargeable sealed lead-
acid batteries (See “Battery maintenance” on page 55).
Batteries are located inside the control panel cabinet and must be installed in
series. Polarity must be observed. Connect batteries to the BAT connector on the
control panel PCB.
Note:
If the control panel indicates a Supply Fault, then the batteries may need
to be replaced.
Caution:
No other equipment may be connected to the BAT connector.
Connecting expansion boards
WARNING:
Always disconnect the control panel from the mains power supply
before installing an expansion board.
See your expansion board installation sheet for detailed installation information.
Connecting a fire network
Note:
See your network board installation sheet for detailed installation and
connection information.
Each network board has two ports. Each port is connected (point to point) to the
corresponding ports of the network board in another control panel.
Figure 10: Network board connections
Two wiring options are possible:
• Ring configuration
• Bus
configuration
Содержание KFP-AF Series
Страница 1: ...P N 501 405103 1 10 REV 1 0 ISS 20NOV09 KFP AF Series Installation Manual...
Страница 16: ...Chapter 2 Installation 12 KFP AF Series Installation Manual Figure 4 Mounting hole locations...
Страница 66: ...Chapter 5 Technical specifications 62 KFP AF Series Installation Manual Figure 17 Cabinet dimensions and views...
Страница 74: ...Appendix B Menu maps 70 KFP AF Series Installation Manual...
Страница 77: ...KFP AF Series Installation Manual 73...
Страница 78: ...74 KFP AF Series Installation Manual...
Страница 79: ......
Страница 80: ......