7. Controller disassembly.
If controller disassembly is necessary follow the following procedure:
– Disconnect the boiler and controller from power supply,
– Remove the controller from the boiler,
– Disconnect terminals and wires from the controller.
8. Technical Data.
Power Supply
230 V ± 10%, 50 Hz
Power consumption (without fan and pump)
< 2 VA
Temperature measurement range (KTY 81-210)
-39–109°C±1°C
Temperature measurement range (PT-1000)
-30–500°C±3°C
Boiler temperature adjustment range
30–90°C±1°C
Boiler programmed overheating protection
90–99°C±1°C
Boiler equipment overheating protection
>95°C±1°C
Total outputs rating
max 2 A / 230 V
Dimensions (H x W x D)
96 x 144 x 94