12
1.13 Current furnace brightness (FD–1).
1.14 Ignitor turn-off depending on the illuminance value.
0
255
1.15 Burner running time.
1.16 Number of inflammation burner.
1.17 Boiler is turned on.
NIE
TAK
1.18 DHW heating is turned on.
NIE
TAK
1.19 Alarms cancellation.
1.20 Burner working mode. (CONTINUOUS), CYCLIC)
1.21 SUMMER threshold temperature.
1°C
30°C
1.22 WINTER threshold temperature.
0°C
29°C
1.23 Increasing the temperature of the boiler.
NIE
TAK
1.24 Heating circuit 2.
NIE
TAK
1.1 Fuel type selection –
RK-2006SPGM controller enables programming ignition
settings for four different fuel types. „Fuel type” parameter enables switching betwe-
en particular settings. Fan, auger and igniter operation are saved for the selected
fuel type. PELLET 1,2,3 and WOOD. When the WOOD fuel is set, you can burn the
wood in the pellet boiler – the controller operates at the wood fuel burning settings.
WOOD/PELLET – once the wood has been burned, the controller switches to pellet
burning and full service to the pellet boiler is provided.
CAUTION!
Fuel type may be changed, if the controller is in STOP mode only.
1.2 Desired boiler temperature
– it is the temperature setting that will be obtained
by the controller, if room thermostat input contacts are closed.
1.3 Boiler operation max. power
– boiler operation max. power – this parameter
enables to limit boiler operation max power. Power limitation is possible thanks to
fuel reduction during operation at maximum power.
1.4 CH pump work mode – WINTER/SUMMER/AUTO
– you can turn off the hea-
ting during summer by selecting the SUMMER value. The parameter indicates the
CH pump work will be turned off. When in the mode, the regulator controls the boiler
to feed the domestic hot water circulation only.