10
CAUTION!
This alarm may be cancelled only if the auger temperature drops below
set point. If the alarm was cancelled before extinction completion, only sound alarm
will be turned off.
Auger sensor damage
.
In case of auger temperature sensor damage, as in case of overheating, the control-
ler will go to shut down mode and will activate the appropriate alarm:
CAUTION!
This alarm may be cancelled only after repairs. Burner temperature sen-
sor damage. If flame temperature detector (CT-1/2 or PT-1000) has been connected
to the controller, its damage will result in activation of the alarm and switching into
STAND-BY mode.
Protection against overheating and overheating of the boiler.
RK-2006SPGM is protected against overheating of the boiler. If the water temperatu-
re reaches a preset value in parameter TEMP service. MAXIMUM THE BOILER, the
controller activates the pump absolutely CO. The increase in water temperature in
the boiler to the value programmed in parameter service TEMPERATURE BOILER
OVERHEAT will turn off the fan, heating pump, switch the controller to STOP mode
without starting the process of extinction and trigger the alarm:
CAUTION!
This alarm may be cancelled, if boiler water temperature drops below the
overheating temperature setting.
Boiler temperature sensor damage.
In case of boiler water temperature sensor damage the controller turns off the fan,
engages central heating pump, controller switches into STOP mode and activates
alarm:
CAUTION!
This alarm may be cancelled, only if repairs are made.
Damage to the outside temperature sensor.
In the event of damage to the external temperature sensor controller causes alarm -
the minimum temperature is maintained in the circuits dependent the outside tempe-
rature.
Damage to the temperature sensor circuit 2.
In the event of damage to the temperature sensor circuit 2 controller triggers an
alarm - 2 heating circuit is switched off.