Operation instruction:
1. Some parameters setting range of the air-cooled scroll chiller is smaller than the LNS setting range,
please refers to the setting expected value of the operation manual of the Air-cooled Scroll;
2. When use the LNS to operate the air-cooled scroll chiller, it is suggested that set the mode, the setting
temperature to reach the expected effect.
14.6 K01-BACNET KEM gateway (Optional)
14.6.1 Features
Insert Air conditioner system to K01-BACNET KEM.
Comply with K01-BACNET KEM Standard, base on K01-BACNET KEM technique.
The core control module of node applies Flash Memory, which application program could be downloaded
and upgrade on line.
Support K01-BACNET KEM/IP Protocol, Ethernet connected way. Support four 485 interfaces, convenient
for installation and wiring.
14.6.2 Technical Specifications
No.
Function
Description
1
Processor
SAMSUNG ARM9 S3C2410
2
Memory
HY57V561620T 133MHZ 64M
3
Saver
SAMSUNG K9F 1208VOB 64M
4
I/O
4 road 485 interface
5
K01-BACNET KEM
connection
K01-BACNET KEM/IP
6
Input supply power
220V AC
7
Work temperature
Temperature 0~50 Relative humidity 25~90%
8
Mass of function
See owner's manual
9
Dimension
26cmX25cmX6cm
14.6.3 Function description
This unit shall be installed between in Building Management System (BMS) and air conditioning, which
provide with K01-BACNET KEM interfaces, associating these two systems to realize the systems
integration.
BMS is allowed to access any online air conditioning in central air conditioning system for information
collection and operation control, after proper installation of central air conditioning and this unit.
NO
Name
Current of
Compressor A
5
6
Network
variable name
nvoCompA
Current[n]
SNVT_count
0~250A
Current of
Compressor B
nvoCompB
Current[n]
SNVT_count
0~250A
Network
variable type
Date definition
Descriptions
Compressor A current
of unit.
*n means the address of
the unit,
nvoCompACurrent[1]
means the Compressor A
current of unit which
address is 1.
Compressor B current
of unit.
*n means the address of
the unit,
nvoCompBCurrent[1]
means the Compressor B
current of unit which
address is 1.
Содержание KEM-30 DNH3
Страница 2: ......
Страница 5: ...2 1 2 External appearance KEM 130 HN3 KEM 200 HN3 KEM 250 HN3 KEM 30 DHN3 KEM 65 DHN3 ...
Страница 33: ...30 130kW module ...
Страница 34: ...MCAC ATSM 2017 08 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 31 200kW module ...
Страница 35: ...32 250kW module ...
Страница 39: ...36 200kW module ...
Страница 40: ...MCAC ATSM 2017 08 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 37 250kW module ...
Страница 73: ...130kW module 200kW module Input of airflow Input of airflow Input of airflow Input of airflow ...
Страница 159: ......
Страница 160: ......