MCAC-ATSM-2017-08 Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz)
3
2 Features
1). Low ambient temperature cooling function
the ambient temperature is down to -10
in cooling mode with low ambient kit
this function should be
activated by S8 switch on the PCB board.
Mode
Ambient temp.
Cooling
Normally
S8 address OFF
10~46
Low temp. (S8 address ON)
-10~46
2). Wide range of outlet water temperature
Cooling: 5~17˚C (Set in factory), 0~17˚C can be available by switch the S5 on PCB, the antifreeze must be
put into water system.
Heating: 40~50˚C (Set in factory), 22~50˚C can be available by switch the address.
Mode
Outlet water temp.
Cooling(S5 address)
Default(OFF)
5~17
Low water temp.(ON)
0~17
Heating(S4 address)
Default (OFF)
40~50
Low water temp. (ON)
22~50
3).Digital scroll technique
When the system operates at the part-load, the system can accurately adjust cooling and heating capacity
output basing on actual requirement of the indoor room. Digital scroll technique, provide maximum reliability,
high efficiency and quiet operation.
4).Modular design, flexible combination
The unit adopts modular design, which can make more units to connect together. The unit can be combined
max16 modules (30&65kW module),5 modules (200kW module) or 8 modules (130&250kW
module),meanwhile every separate module can be operated as main unit, also each module can be a slave
unit with modules combination(The digital unit must be operated as main unit if the system has digital unit.),
more convenient for design and installation.
5).Easy connection between main unit and slave units.
All the units can be connected together with a wired controller in series type. Using three-core shielded
twisted wire as communication wire.
Max 8 modules
2000kW
250kW
250kW
0
25
50
75
100
1.2
60
120
180 240
Capacity output
(%)
Capacity output of digital scroll air-cooled chiller system
(100%)ON
(0%)OFF
Capacity output of traditional air-cooled scroll chiller system
Содержание KEM-30 DNH3
Страница 2: ......
Страница 5: ...2 1 2 External appearance KEM 130 HN3 KEM 200 HN3 KEM 250 HN3 KEM 30 DHN3 KEM 65 DHN3 ...
Страница 33: ...30 130kW module ...
Страница 34: ...MCAC ATSM 2017 08 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 31 200kW module ...
Страница 35: ...32 250kW module ...
Страница 39: ...36 200kW module ...
Страница 40: ...MCAC ATSM 2017 08 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 37 250kW module ...
Страница 73: ...130kW module 200kW module Input of airflow Input of airflow Input of airflow Input of airflow ...
Страница 159: ......
Страница 160: ......