48
9.5 KEM-250 HN3
Cooling:
Chilled water outlet
temp.
Ambient temp.(
)
21.00
25.00
30.00
35.00
40.00
46.00
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(
)
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
5.00
279.89
68.96
263.55
71.09
248.63
73.29
235.00
75.56
220.20
79.34
202.58
83.30
6.00
289.34
70.03
272.19
72.20
256.54
74.43
242.25
76.73
227.23
80.57
209.28
84.60
7.00
299.44
71.46
281.43
73.67
265.00
75.95
250.00
78.30
234.75
82.22
216.44
86.33
8.00
308.70
73.61
289.86
75.88
272.68
78.23
257.00
80.65
241.58
84.68
222.98
88.92
9.00
317.40
74.32
297.75
76.62
279.84
78.99
263.50
81.43
247.95
85.50
229.11
89.78
10.00
329.43
75.44
308.75
77.77
289.90
80.17
272.72
82.65
256.90
86.79
237.64
91.13
11.00
338.62
76.18
317.06
78.53
297.43
80.96
279.54
83.47
263.61
87.64
244.10
92.02
12.00
346.37
77.29
324.01
79.68
303.66
82.15
285.13
84.69
269.16
88.92
249.52
93.37
13.00
352.55
77.91
329.49
80.32
308.51
82.81
289.41
85.37
273.49
89.64
253.80
94.12
14.00
361.32
78.45
337.37
80.88
315.59
83.38
295.78
85.96
279.80
90.26
259.94
94.77
15.00
365.96
78.84
341.38
81.28
319.05
83.79
298.73
86.38
282.90
90.70
263.10
95.24
Note:
The inlet/outlet water temperature difference is 5
.
Содержание KEM-30 DNH3
Страница 2: ......
Страница 5: ...2 1 2 External appearance KEM 130 HN3 KEM 200 HN3 KEM 250 HN3 KEM 30 DHN3 KEM 65 DHN3 ...
Страница 33: ...30 130kW module ...
Страница 34: ...MCAC ATSM 2017 08 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 31 200kW module ...
Страница 35: ...32 250kW module ...
Страница 39: ...36 200kW module ...
Страница 40: ...MCAC ATSM 2017 08 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 37 250kW module ...
Страница 73: ...130kW module 200kW module Input of airflow Input of airflow Input of airflow Input of airflow ...
Страница 159: ......
Страница 160: ......