Fouling Factor
ALTITUDE
(m)
Difference of water
inlet and outlet temp.
( )
Fouling Factor
0.018 /kW
0.044m 2 /kW
0.086m 2 /kW
0.172m 2 /kW
C
P
C
P
C
P
C
P
Sea level
3
1.036
1.077
1.019
1.076
0.991
0.975
0.963
0.983
4
1.039
1.101
1.022
1.080
0.994
0.996
0.971
0.984
5
1.045
1.105
1.028
1.086
1.000
1.000
0.977
0.989
6
1.051
1.109
1.034
1.093
1.006
1.004
0.983
0.994
600
3
1.024
1.087
1.008
1.064
0.980
0.984
0.951
0.991
4
1.027
1.111
1.011
1.068
0.983
1.005
0.959
0.992
5
1.034
1.115
1.017
1.074
0.989
1.009
0.965
0.997
6
1.043
1.115
1.026
1.084
0.998
1.009
0.973
0.999
1200
3
1.013
1.117
0.996
1.052
0.969
1.011
0.942
1.002
4
1.015
1.118
0.998
1.055
0.971
1.012
0.948
1.003
5
1.023
1.122
1.006
1.063
0.979
1.015
0.955
1.005
6
1.031
1.125
1.015
1.072
0.987
1.018
0.962
1.007
1800
3
1.002
1.128
0.986
1.042
0.959
1.021
0.935
1.007
4
1.005
1.129
0.989
1.045
0.962
1.022
0.941
1.010
5
1.012
1.132
0.995
1.051
0.968
1.024
0.945
1.012
6
1.018
1.134
1.001
1.058
0.974
1.026
0.949
1.014
C--Cooling capacity
P--Power
11.2.3 Installation & regulation guide for water flow switch
● Please carefully check flow switches before conducting installation of the water flow switch. Packing
should be in good condition, and the appearance should be free of damage and deformation. If any problem,
please contact the manufacturer.
● Flow switches can be installed in the horizontal pipeline or the vertical pipeline with upward flowing
direction but cannot be mounted in the pipeline with downward flowing direction. The inlet water of gravity
should be taken into account when flow switches are installed in the pipeline with upward flowing direction.
●Water flow switch must be installed on a section of straight-line pipeline, and its both ends must be
supplied with straight-line pipes whose length is at least 5 times diameter of the pipe. In the meanwhile, the
fluid flowing direction in the pipeline must be consistent with the direction of arrow on the controller. The
connection terminal should be located where wiring connection can be easily done.
● Pay attention to the following items when conducting installation and wire connection:
a. Collision of the wrench with the soleplate of the flow switch is prohibited, since such collision may cause
deformation and failure of the flow switch.
b. To avoid electric shock and damages to the devices, the power supply should be cut off, when wires are
connected or adjustment is done.
c. When wiring connection is conducted, adjustment of other screws except connection terminals of micro
switches and ground screws is prohibited. In the meanwhile, over great force should not applied when wires
of micro switches are connected, otherwise micro switches may suffer displacement, thus leading to failure
of flow switches.
Содержание KEM-30 DNH3
Страница 2: ......
Страница 5: ...2 1 2 External appearance KEM 130 HN3 KEM 200 HN3 KEM 250 HN3 KEM 30 DHN3 KEM 65 DHN3 ...
Страница 33: ...30 130kW module ...
Страница 34: ...MCAC ATSM 2017 08 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 31 200kW module ...
Страница 35: ...32 250kW module ...
Страница 39: ...36 200kW module ...
Страница 40: ...MCAC ATSM 2017 08 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 37 250kW module ...
Страница 73: ...130kW module 200kW module Input of airflow Input of airflow Input of airflow Input of airflow ...
Страница 159: ......
Страница 160: ......