14 Control System
14.1 PCB Outline and Description
14.1.1 PCB outlook view
14.1.2 Components description
No. Detail information
1
Detection of current of the compressor A1 (Protection code P4).
2
Detection of current of the compressor B1 (Protection code P5).
Current is not detected within the initial 5 seconds after the compressor is started up. When the current of the compressor is
detected to exceed protective value set (18A for constant speed compressor), it will be shut down and re-started after 3
min.
3
T4: outdoor ambient temperature sensor (Fault code E7).
T3B: pipe temperature sensor of the condenser B (Fault code E6 and protection code P7).
T3A: pipe temperature sensor of the condenser A (Fault code E5 and protection code P6).
1) T4: if there is one system that requires starting outdoor fans, the fans are started through electric control of the unit. Start
outdoor fan A only, start A and B gears, and control the unit through T4.
2) T3B and T3A: when the electric control of the unit detects the temperature of the outdoor pipe T3A or T3B of the system
exceeds the protective temperature 65 , the corresponding system will be shut down. And it will be re-started up, after the
Содержание KEM-30 DNH3
Страница 2: ......
Страница 5: ...2 1 2 External appearance KEM 130 HN3 KEM 200 HN3 KEM 250 HN3 KEM 30 DHN3 KEM 65 DHN3 ...
Страница 33: ...30 130kW module ...
Страница 34: ...MCAC ATSM 2017 08 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 31 200kW module ...
Страница 35: ...32 250kW module ...
Страница 39: ...36 200kW module ...
Страница 40: ...MCAC ATSM 2017 08 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 37 250kW module ...
Страница 73: ...130kW module 200kW module Input of airflow Input of airflow Input of airflow Input of airflow ...
Страница 159: ......
Страница 160: ......