MCAC-ATSM-2017-08 Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz)
129
2 Detail procedures of modify a Weekly Timing Schedule:
a Select a wired controller: By clicking the
System diagram for weekly timing AC wired controller icon
at the left side in the wired controller, or by selecting the wired controller at the drop-down box of
KJR
Address .
b Select a wired controller: By clicking the Period of the System diagram for weekly timing AC at the left
side in the wired controller, or by selecting the wanted modified Period at the drop-down box of
Period .
c Detail parameter for modifying weekly timing schedule:
Time On Turn on time, when Time On selecting
-- -- , then means do not turn on the unit , display as
Fig 4-44.
Time Off Turn off time, when Time Off selecting
-- -- , then means do not turn off the unit , display as
Fig 4-45.
Timing Status Drive up the weekly timing function in the current period or not.
Control Mode Automatically drive-up mode
Mode set Heating Cooling Water Pump
Setting temp. Setting temp.
If other parameters have been set, click “Save” key, a message box as the same as above” (1) Detail
procedures of add a new Weekly Timing Schedule” will pop up.
Once the setting time is reach, system will set according to the setting parameter, window as Fig. 4-46 will
display. When finish the set up, message box will close automatically.
Error record
Save the system operation error record, includes: Record time, Error prevented cord,
Sub-module address and KJR address (see Fig. 4-47); click the
Record time
Protection code
Sub-module address
KJR address can proceed ordering(see Fig 4-48) ;“Clear all record ”in the Menu
(See Fig. 4-49) could be used to delete all error records.
Fig.4-44
Fig.4-45
Fig.4-46
Fig.4-43
Содержание KEM-30 DNH3
Страница 2: ......
Страница 5: ...2 1 2 External appearance KEM 130 HN3 KEM 200 HN3 KEM 250 HN3 KEM 30 DHN3 KEM 65 DHN3 ...
Страница 33: ...30 130kW module ...
Страница 34: ...MCAC ATSM 2017 08 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 31 200kW module ...
Страница 35: ...32 250kW module ...
Страница 39: ...36 200kW module ...
Страница 40: ...MCAC ATSM 2017 08 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 37 250kW module ...
Страница 73: ...130kW module 200kW module Input of airflow Input of airflow Input of airflow Input of airflow ...
Страница 159: ......
Страница 160: ......