![Kampmann KaDeck Series Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/kampmann/kadeck-series/kadeck-series_installation-and-operating-instructions-manual_3354081035.webp)
35
KaDeck
3.26
Versatile air conditioning for offices and administration buildings
Installation and operating instructions
Wiring of stand-alone KaControl
Cabling for groups of up to 6 individual KaControl units
Accessory: Operating unit with temperature
measurement: 196003210001 or
196003210002
230V / 50Hz
Accessories: Room sensor,
196003250110
3 *
2 **
max.
30
m
3 **
* Connection e.g. as NYM, sized according to cable length.
** CAT5 connection (AWG 23 or equivalent), linear wiring.
* Connection e.g. as NYM, sized according to cable length.
** CAT5 connection (AWG 23 or equivalent), linear wiring.
Potential-free input and H/C sensors can be used
for the master unit.
If you wish, you can separately measure the
temperature for each unit via a room or air
intake sensor.
Temperature detection
with group control
The air intake temperature
is used for regulation with
group control.
Every ceiling cassette
regulates based on its
own measured air intake
temperature – with the value
set on the KaController acting
as the setpoint for all units in
the group.
Maximum permissible cable lengths
Total length of BUS cables between the KaDeck units
max. 30 m
Total length of BUS cable between the room control unit and master unit
max. 30 m
Total length between the KaDeck and the external potential-free contacts e.g. window contact etc.
max. 30 m
Total length between the KaDeck and the separate room temperature sensor
max. 30 m
Accessories: Operating unit with temperature
measurement: 196003210001 or 196003210002
Total per group,
max. 6 units
Maximum length of bus connection: 30 m
Maximum length of bus connection: 30 m