6.5 Water connection with wet cooling
We recommend using Kampmann-side accessories to provide
the heat exchanger connections with the valves and on-site
pipework. Coordinate the on-site valves, hoses etc. to the
available space and requirements of the KaDeck.
Remove the condensation tray to connect up the water
connection. First check whether there is water in the tray or the
pipework. Dismantle the tray, as described under section 8.3.3
First fit the flexible hose to the angle valve (including sealing
work) and then the angle valve to the KaDeck. Now the
actuator can be fitted and the cable routed to the electrical
connection area.
Use the clamps on the fan for this purpose.
Now fit the components for the return in the same
order and route the flexible connections to the
required outlet on the unit. Connect up the on-site water
network and insulate the pipes and flexible hoses as far as the
valve. Use vapour-impermeable insulation for this. Make sure
that any condensation that forms drips from the pipework and
the insulation into the condensation tray.
Check whether the hoses have been damaged
or bent by the work and are still fixed in the fixing clips before
fitting the tray.
Insert the condensation tray into the fixings provided for this
purpose and check whether the tray is fitted horizontally.