KaDeck
Versatile air conditioning for offices and administration buildings
Installation and operating instructions
Important note:
Provide an all-pole mains separator in the wiring on
site that can be reliably secured to avoid the system
being reconnected (e.g. a lockable switch with a
contact opening of at least 3 mm up to a rated
voltage of 480 V).
No protective measures are indicated on
Kampmann wiring diagrams. These must be
provided additionally when installing the system
and when connecting the units in accordance
with VDE 0100 and the regulations of each of the
respective energy supply companies.
Cabling
Ask a qualified electrician to determine the type of cable and
cable cross-sections: the cable cross sections basically depend on
the fuses for the cable length and the wiring capacity of the
electric motors on site .
Lay control lines separately from supply lines.
Use CAT5 (AWG 23) or similar as data cables.
Wire the unit in series: star cabling is not allowed.
6.8 Overview of Controls
The unit comes in a series of different electrical versions.
Connect it via a terminal strip in the electrical junction box.
which is located on the opposite side of the unit's water
connection.
Wire the unit as per the wiring diagram, which is different for
each version.
Example:
326026211211C1
-> Dry cooling with KaControl without dew point monitor
models
Art. no. suffix
EC fans, electromechanical model
_00
EC fans, KaControl control electronics
_C1