11. Error Codes
Operation lamp
Timer lamp
Display
LED status
1 time
X
E0
Indoor unit EEPROM parameter error
2 times
X
E1
Indoor / outdoor units communication error
4 times
X
E3
Indoor fan speed has been out of control
5 times
X
E4
Indoor room temperature sensor T1 open circuit or short circuit
6 times
X
E5
Evaporator coil temperature sensor T2 open circuit or short circuit
7 times
X
EC
Refrigerant leakage detection
1 times
O
F0
Overload current protection
2 times
O
F1
Outdoor ambient temperature sensor T4 open circuit or short circuit
3 times
O
F2
Condenser coil temperature sensor T3 open circuit or short circuit
4 times
O
F3
Compressor discharge temperature sensor T5 open circuit or short circuit
5 times
O
F4
Outdoor unit EEPROM parameter error
6 times
O
F5
Outdoor fan speed has been out of control
1 times
P0
IPM malfunction or IGBT over-strong current protection
2 times
P1
Over voltage or over low voltage protection
3 times
P2
High temperature protection of IPM module or compressor top
5 times
P4
Inverter compressor drive error
O (light)
X (off)
(flash)
*Fault Symptom: The display board shows a garbled code or a code that is not an error code found in the service
manual nor a temperature reading.
Trouble shooting:
Use the remote controller. If the unit does not respond to the remote, the indoor PCB needs to be replaced;
if the unit does respond, then the display board needs to be replaced.
J3387_Kaden_Installer_Manual_050917.indd 33
5/09/2017 9:08 AM
Содержание KS09
Страница 2: ...J3387_Kaden_Installer_Manual_050917 indd 2 5 09 2017 9 07 AM...
Страница 34: ...34 Kaden Installation Manual Notes J3387_Kaden_Installer_Manual_050917 indd 34 5 09 2017 9 08 AM...
Страница 35: ...Kaden Installation Manual 35 Notes J3387_Kaden_Installer_Manual_050917 indd 35 5 09 2017 9 08 AM...
Страница 36: ...J3387_Kaden_Installer_Manual_050917 indd 36 5 09 2017 9 08 AM...