Kaden Installation Manual |
27
Outer Diameter of Pipe (mm)
Tightening Torque (N•m)
Add. Tightening Torque (N•m)
Ø 6.35 (Ø 0.25”)
15
16
Ø 9.52 (Ø 0.375”)
25
26
Ø 12.70 (Ø 0.5”)
35
36
Ø 15.88 (Ø 0.63”)
45
47
6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool clockwise until the pipe is
fully flared.
8. Remove the flaring tool and flare form, then inspect the end
of the pipe for cracks and even flaring.
Step 4: Connect pipes
When connecting refrigerant pipes, be careful not to use
excessive torque or to deform the piping in any way.
You should first connect the low-pressure pipe, then
the high-pressure pipe.
Minimum bend radius
When bending connective refrigerant piping, the minimum
bending radius is 10cm. See
Fig.5.6
≥10cm (4in)
Radius
Fig. 5.6
Instructions for connecting
piping to indoor unit
1. Add refrigerant oil to the flare faces.
2. Align the center of the two pipes that you will connect.
See
Fig. 5.7
Indoor unit tubing
Flare nut
Pipe
Fig. 5.7
3. Tighten the flare nut as tightly as possible by hand.
4. Using a spanner, grip the nut on the unit tubing.
5. While firmly gripping the nut on the unit tubing, use a torque
wrench to tighten the flare nut according to the torque
values in the
Torque Requirements
table below.
Loosen the flaring nut slightly, then tighten again.
Fig. 5.8
Torque Requirements
Do not use excessive torque
Excessive force can break the nut or damage the refrigerant piping. You must not exceed torque requirements
shown in the table above.
J3387_Kaden_Installer_Manual_050917.indd 27
5/09/2017 9:08 AM
Содержание KS09
Страница 2: ...J3387_Kaden_Installer_Manual_050917 indd 2 5 09 2017 9 07 AM...
Страница 34: ...34 Kaden Installation Manual Notes J3387_Kaden_Installer_Manual_050917 indd 34 5 09 2017 9 08 AM...
Страница 35: ...Kaden Installation Manual 35 Notes J3387_Kaden_Installer_Manual_050917 indd 35 5 09 2017 9 08 AM...
Страница 36: ...J3387_Kaden_Installer_Manual_050917 indd 36 5 09 2017 9 08 AM...