| Kaden Installation Manual
Step 2: Remove burrs
Burrs can affect the tight seal of refrigerant piping connection.
They must be completely removed.
1. Hold the pipe at a downward angle to prevent burrs from
falling into the pipe.
2. Using a reamer or deburring tool, remove all burrs from the
cut section of the pipe.
Pipe
Reamer
Point down
Fig. 5.2
Step 3: Flare pipe ends
Proper flaring is essential to achieve a tight seal.
1. After removing burrs from cut pipe, seal the ends with PVC
tape to prevent foreign materials from entering the pipe.
2. Sheath the pipe with insulating material.
3. Place flare nuts on both ends of pipe. Make sure they are
facing in the right direction, because you can’t put them on
or change their direction after flaring. See
Fig. 5.3
Flare nut
Copper pipe
Fig. 5.3
4. Remove PVC tape from ends of pipe when ready to
perform flaring work.
5. Clamp flare form on the end of the pipe. The end of the
pipe must extend beyond the edge of the flare form in
accordance with the dimensions shown in the table below.
Fig. 5.4
Flare Connection Size (A)
A (mm)
Min.
Max.
Ø 6.35 (Ø 0.25”)
0.7 (0.0275”)
1.3 (0.05”)
Ø 9.52 (Ø 0.375”)
1.0 (0.04”)
1.6 (0.063”)
Ø 12.70 (Ø 0.5”)
1.0 (0.04”)
1.8 (0.07”)
Ø 15.88 (Ø 0.63”)
2.0 (0.078”)
2.2 (0.086”)
Flare form
Pipe
A
Fig. 5.5
Do not deform pipe
while cutting
Be extra careful not to damage, dent, or deform the
pipe while cutting. This will drastically reduce the
heating efficiency of the unit.
J3387_Kaden_Installer_Manual_050917.indd 26
5/09/2017 9:08 AM
Содержание KS09
Страница 2: ...J3387_Kaden_Installer_Manual_050917 indd 2 5 09 2017 9 07 AM...
Страница 34: ...34 Kaden Installation Manual Notes J3387_Kaden_Installer_Manual_050917 indd 34 5 09 2017 9 08 AM...
Страница 35: ...Kaden Installation Manual 35 Notes J3387_Kaden_Installer_Manual_050917 indd 35 5 09 2017 9 08 AM...
Страница 36: ...J3387_Kaden_Installer_Manual_050917 indd 36 5 09 2017 9 08 AM...