Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Gradient
0 – 200 [% Pref /
Hz] / 40 [% Pref /
Hz] / 1
F
Set gradient of power limitation function with increasing frequency.
This percentage relates to the nominal frequency of 50 Hz.
Determines the active power reduction subject to the frequency.
The active power is reduced by a gradient in %-P
ref
. In the event of a fre-
quency deviation of one Hz, the configured reduction of the output
power is carried out. The percentage value relates to P
ref
, the actual
power level at the time the frequency exceeds the configured activation
threshold (PM).
NOTE: A drop in the range of 2 % to 12 % corresponds to a
gradient in the range of 100 %/Hz to 16 %/Hz.
4
1
2
3
4
Steigung bei fallender
Frequenz
0 – 200 [% Pref/
Hz] / 40 [% Pref/
Hz] / 1
F
Specify gradient in the case of a decreasing frequency as a %
0
(per
thousand) / minute (if mode "1" or mode "2" is active).
4
1
2
3
4
Activation threshold at
underfrequency
40 – 60 [Hz] / 0.01
[Hz]
Activation threshold at
overfrequency
50 – 70 [Hz] 0.01
[Hz]
1. Frequency thresholds for activating the power limitation with un-
dervoltage.
2. Frequency thresholds for activating the power limitation with over-
voltage.
4
1
2
3
4
P(f) intentional delay
0 – 5,000 [ms] / 0
[ms] 1
F
Set delay of the power limitation.
Not at IL, IT
4
1
2
3
4
P(f) Deaktivierungszeit
0 – 6000000 [ms] /
0 [ms] / 1000 [ms]
F
Specify time for power reduction (if mode 1 is active).
4
1
2
3
4
P(f) deactivation gradi-
ent
0 – 65,534 [% Smax /
min] / 10 / 1
F
Specify deactivation gradient.
4
1
2
3
4
Dynamic gradient
mode
On | Off
F
Activate dynamic gradient.
4
1
2
3
4
P(f) minimum deactiva-
tion frequency
45 – 61.5 [Hz] /
0.01 &
P(f) maximum deacti-
vation frequency
45 – 70 [Hz] / 0.01
F
Specify the minimum deactivation frequency in Hz.
NOTE: Only evaluated in mode 1.
The function is disabled if the frequency returns to the range between
the minimum and maximum deactivation threshold and remains within
this range for the duration of the deactivation time.
4
1
2
3
4
Maximum dynamic gra-
dient frequency
50.22 – 70.5 [Hz]
Minimum dynamic gra-
dient frequency
45 – 50 [Hz]
F
Specify the dynamic gradient frequency in Hz.
9 | Configuration and operation
Manual
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
Page 56