![Kaco blueplanet gridsave 92.0 TL3-S Скачать руководство пользователя страница 55](http://html1.mh-extra.com/html/kaco/blueplanet-gridsave-92-0-tl3-s/blueplanet-gridsave-92-0-tl3-s_manual_3159052055.webp)
Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Q(U) active curve
1 - 4
F
Select the active curve.
NOTE: Up to 4 characteristic curves can be configured inde-
pendently and one of them can be activated for regulation
each time.
4
1
2
3
4
Priority mode
Q-Priority | P-Prior-
ity
F
Set priority for reactive power - Q or active power - P.
NOTE: When it comes to P priority, the reactive power adjust-
ment range is limited subject to the active power that is cur-
rently available and fed in.
4
1
2
3
4
Number of nodes
2 - 10
NOTE: The maximum number of configurable nodes depends
on the selected grid type.
F
Specify the number of nodes.
4
1
2
3
4
Node 1- Node 10
Power / Excitation /
Voltage
0 – 100 [% Slim] /
43.6 [% Slim] / 0.1
F
Set the reactive power of the node as a percentage of the maximum
power.
Over-excited | un-
der-excited
F
Art der Phasenverschiebung auswählen.
NOTE: Übererregt entspricht einer kapazitiven Last, unter-
erregt entspricht einer induktiven Last.
0 – 125.0 [%
Unom] / 90 … 110.0
[% Unom] / 0.1 [%
Unom]
F
Enter the voltage of the node in volts..
NOTE: The voltage values of the nodes must increase continu-
ously. At voltages below the 1st node and voltages above the
last node, the reactive power value of the 1st or last node is
used each time.
4
1
2
3
4
Frequency dependent
power reduction
NOTE: Activate frequency-dependent power reduction in the
P(f) menu.
Not at IL, IT
4
1
2
3
4
Betriebsmodus
Off | Mode 1 |
Mode 2
F
Specify the operation mode.
4
1
2
3
4
Power reference mode
with underfrequency
Actual power |
Nominal power
Power reference mode
with overfrequency
Actual power |
Nominal power
1. Determine control method for underfrequency.
2. Determine control method for overfrequency.
Manual
Configuration and operation | 9
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
Page 55
EN-US