Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Emergeny charge func-
tion
Active / deactivated
deactivated
WARNING! Use the function only to enable the grid connection when
the actual battery voltage U
DC
,
ACT
is lower than the minimum DC volt-
age U
DC
,
ACT
is lower than the minimum DC voltage
DC,MIN
,that is required
for AC grid connection.
NOTE: Once the Emergency Charge Function is activated, the
inverter is no longer operating within the certified grid code
parameters.
WARNING! Any damage caused directly by the "Emergency
Charge Function" will not be covered under warranty.
UD, IL
4
1
2
3
4
Maximum battery volt-
age
1315 – 1450 [V] /
1315 / 0.1
F
Set increased maximum battery voltage for country setting "User de-
fined" or "Israel".
4
1
2
3
4
Grid Parameters
Input screens for network parameters
4
1
2
3
4
Country & Grid type
NOTE: This option influences the country-specific operating
settings of the device. Please consult KACO service for further
information.
1. Select country and grid type.
2. Observe the note for [See section 9.4.2
Nominal grid voltage &
Nominal grid frequency
Password protection
Status
F
Specify optional nominal grid voltage.
NOTE: The device switches off if the grid frequency deviates
from the nominal grid voltage by more than 9.5Hz.
1. Select optional nominal grid frequency.
2. Activate optional password protection.
3. Activate optional password protection.
4
1
2
3
4
FRT (Fault Ride
Through)
NOTE: The device supports dynamic grid stabilization (Fault
Ride-Through).NOTICE! More detailed information at
4
1
2
3
4
Operating mode –
On | Off
F
Select a control process.
On
: Activates dynamic grid support using dynamic reactive current.
Off
: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
Setting | Manual |Pre-
defined zero current
F
Select a control process.
Priority – Reactive cur-
rent limitation | Active
current priority
F
Select a control process.
4
1
2
3
4
Constant k positive se-
quence dip &
Constant k positive se-
quence swell
k 0 – 10 2 0.1
F
Set amplification factor k for the pos. sequence for drop and increase
in the grid voltage.
Manual
Configuration and operation | 9