Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
Gradient with overfre-
quency – charging
0 – 200 (%/Hz) ; 40
(%/Hz)
Gradient with under-
frequency – charging
0 – 200 (%/Hz) ; 40
(%/Hz)
Gradient with overfrequency (charging):
Determines the active power adjustment in accordance with equation 2
and equation 3, subject to the frequency.
Gradient for overfrequency incidents if the incident begins in charging
mode.
Gradient with underfrequency (charging):
Determines the active power adjustment in accordance with equation 2
and equation 3, subject to the frequency.
Gradient for underfrequency incidents if the incident begins in charging
mode.
Gradient
0 – 200 (%/Hz) ; 66
(%/Hz)
Determines the active power adjustment in accordance with [See figure
58 [
Page 73], subject to the frequency.
Maximum dynamic gra-
dient frequency
50,22 – 70,5 [Hz]
0.01 [Hz]
Minimum dynamic gra-
dient frequency
45 – 50 [Hz] 0.01
[Hz]
Dynamic gradient maximum frequency:
If dynamic gradient mode is activated, the gradient is calculated in order
to guarantee a linear power adjustment and reach the maximum charg-
ing power if the frequency rises to the maximum configured frequency.
Dynamic gradient minimum frequency:
If dynamic gradient mode is activated, the gradient is calculated in order
to guarantee a linear power adjustment and reach the maximum feed-in
power if the frequency drops to the minimum configured frequency.
Activation threshold
with underfrequency:
40 – 50 [Hz] / 40
[Hz] / 0.01
Activation threshold
with overfrequency:
50 – 60 [Hz] /
50.02 [Hz] / 0.01
Activation threshold (f1) underfrequency:
Determines the frequency threshold for activating the function in case
of underfrequency incidents. The active power adjustment is activated if
the frequency falls below the configured value and mode 1 or 2 is acti-
vated.
In mode 2, the function is deactivated if the frequency rises above the
configured value.
Activation threshold (f1) overfrequency:
Determines the frequency threshold for activating the function in case
of overfrequency incidents. The active power adjustment is activated if
the frequency rises above the configured value and mode 1 or 2 is acti-
vated.
In mode 2, the function is deactivated if the frequency falls below the
configured value.
Threshold Area lower
limit [Hz]
40 – 50 [Hz] / 47.5
[%/Hz] / 0.01
Only evaluated in mode 1.
The function is deactivated if the frequency returns to the deactivation
range and remains in this range for the duration of the deactivation
time.
Threshold Area upper
limit [Hz]
50 – 60 [Hz] / 50.5
[Hz] / 0.01
P(f) Deaktivierungszeit
0 – 6,000,000 [ms] /
0 [ms] 1
Only evaluated in mode 1.
The function is disabled if the frequency returns to the range between
the minimum and maximum deactivation threshold and remains within
this range for the duration of the deactivation time.
Manual
Specifications | 10
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
Page 75