Time required for connecting the interface cables:
1. Observe the instructions on the recommended cable for the interface used.
2. Open the housing door.
3. Unfasten the cover on the cable fitting [ W_20].
4. Feed the signal cable into the connection area.
ð
Signal cable inserted.
Inserting the Ethernet cable.
1. Unfasten and remove the cover on the cable fitting [ W_29].
2. Remove the sealing insert.
3. Pass the connection cable through the cover of the cable fitting and the sealing
insert.
4. Insert the sealing insert into the cable fitting.
5. Feed the connection cables into the connection area.
ð
Ethernet cable inserted.
1
2
Fig. 28:
Insert signal cables
1 Cable fitting for routing the Eth-
ernet cable
2 Cable fitting for routing the sig-
nal cable
7.8.3
Connecting via Ethernet
NOTE
The connection plug of an RJ45 cable is larger than the opening of an M25 cable fitting when it is installed. For
this reason, remove the sealing insert before installation and thread the Ethernet cable outside of the cable fit-
ting through the sealing insert.
NOTE
Use a suitable category 7 network cable. The maximum distance between two devices is 100 m (328 ft). The
Ethernet switch allows for the repeater function and supports auto-sensing. Ensure that the cable is correctly
assigned. You can use both crossed and 1:1 protectively-wired Ethernet connection cables.
↻
Connecting cable inside the device.
1. Plug in an Ethernet cable at one of the two Ethernet ports on the communication circuit board.
2. Check that the connecting cable is fitted securely.
ð
Connect additional signal cables.
Connecting the device to the network
↻
The Ethernet cable has been connected to the device.
1. Connect the Ethernet cable to the network or a computer.
2. Configure the Ethernet settings and the webserver in the Settings menu.
7.8.4
Connecting external grid protection components
The contact is designed as an N/O contact and is labeled "ERR" or "Relay" on the circuit board.
Maximum contact load
DC
30 V/1A
↻
Connection area cover open.
1. Loosen the cable fitting to pass the signal cable through [ W_20]
2. Thread the connection cables through the cable fitting.
3. Attach the connection cables to the terminals. [See section 7.8.1
4. Tighten cable fitting [ W_20 / 13,27 In-Ibs ].
7 | Installation
Manual
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
Page 28