2
For this configuration, output power is 4267 W.
3. Calculate input power. In this step, the input power requirements for the example configuration are
calculated. To do this, divide the total output requirement by the efficiency of the power supply as
shown in
NOTE:
Normal-capacity AC and DC power supplies are not included in the following
table, because their power budget was exceeded in the sample configuration.
Table 52: Calculating Input Power for SRX5800 Services Gateway with SCB3, IOC3, and RE2
Input Power Requirement
Power Supply
Efficiency
1
Power Supply
Zone 0: 4177/0.88= 4764 W
~88 %
SRX5800 AC high-capacity
Zone 1: 4267/0.88= 4849 W
Zone 0: 4177/0.86= 4857 W
86 %
SRX5800 DC high-capacity
Zone 1: 4267/0.86= 4962 W
1
These values are at full load and nominal voltage.
4. Calculate thermal output (BTUs) for the system. To calculate this value, add the total input power
requirement (in watts) for the two zones together and multiply the sum by 3.41 as shown in
.
Table 53: Calculating Thermal Output for SRX5800 Services Gateway with SCB3, IOC3, and RE2
Thermal Output (BTUs per hour)
Power Supply
(4764 + 4849) * 3.41 = 32,780 BTU/hr
SRX5800 AC high-capacity
(4857 + 4962) * 3.41 = 33,482 BTU/hr
SRX5800 DC high-capacity
194
Содержание SRX 5800
Страница 1: ...SRX5800 Services Gateway Hardware Guide Published 2020 02 10 ...
Страница 23: ......
Страница 30: ...Figure 2 Rear View of a Fully Configured AC Powered Services Gateway Chassis 31 ...
Страница 111: ...LEDs 112 ...
Страница 121: ...Port and Interface Numbering 122 ...
Страница 127: ...Port and Interface Numbering 128 ...
Страница 161: ......
Страница 179: ... One SRX5K MPC IOC2 Modular Port Concentrator with two Modular Interface Cards MICs 180 ...
Страница 180: ... One SRX5K 40GE SFP I O card IOC 181 ...
Страница 205: ......
Страница 261: ......
Страница 324: ...c Upload the configuration to RE2 from the USB device 325 ...
Страница 365: ...Figure 143 Installing an SPC 366 ...
Страница 367: ...368 ...
Страница 422: ...5 CHAPTER Troubleshooting Hardware Troubleshooting the SRX5800 425 ...
Страница 423: ......
Страница 457: ......
Страница 473: ...475 ...
Страница 476: ...Restricted Access Area Warning 478 ...
Страница 483: ...485 ...
Страница 496: ...Jewelry Removal Warning 498 ...
Страница 499: ...Operating Temperature Warning 501 ...
Страница 509: ...DC Power Disconnection Warning 511 ...
Страница 513: ...DC Power Wiring Sequence Warning 515 ...
Страница 516: ...DC Power Wiring Terminations Warning 518 ...
Страница 519: ...DC Power Disconnection Warning 521 ...
Страница 523: ...DC Power Wiring Sequence Warning 525 ...
Страница 526: ...DC Power Wiring Terminations Warning 528 ...