SRX5800 Rack and Cabinet Requirements
IN THIS SECTION
SRX5800 Services Gateway Rack-Mounting Hardware | 168
SRX5800 Services Gateway Rack Size and Strength Requirements | 168
Spacing of Rack-Mounting Bracket Holes for the SRX5800 Services Gateway | 169
Connection to Building Structure for the SRX5800 Services Gateway Rack | 169
SRX5800 Services Gateway Cabinet Size and Clearance Requirements | 170
SRX5800 Services Gateway Cabinet Airflow Requirements | 170
SRX5800 Services Gateway Rack-Mounting Hardware
The rack-mounting hardware for the SRX5800 Services Gateway includes:
•
The large mounting shelf for mounting in four-post racks, cabinets, and open-frame racks
•
The small mounting shelf for front-mounting in a four-post rack or cabinet
•
Front-mounting flanges on the front of the chassis for front-mounting in a four-post rack or cabinet
•
Two center-mounting brackets attached to the center of the chassis for center-mounting in an open-frame
rack. For an open-frame rack, center-mounting is preferable because of the more even distribution of
weight.
SRX5800 Services Gateway Rack Size and Strength Requirements
The size, strength, and location of the rack must accommodate the services gateway's weight and external
dimensions. The location of the rack must allow for the clearance requirements specified in
Requirements for SRX5800 Services Gateway Airflow and Hardware Maintenance” on page 166
.
The chassis is 17.37 in. (44.11 cm) wide. The services gateway is designed for installation in a standard
19-in. rack, as defined in Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310-D)
published by the Electronics Industry Association (
). The spacing of the holes between
the left and right front-mounting flanges and center-mounting brackets is 18.31 in (465 mm) apart. However,
the inside spacing between the rack rails must allow sufficient space for the width of the chassis.
168
Содержание SRX 5800
Страница 1: ...SRX5800 Services Gateway Hardware Guide Published 2020 02 10 ...
Страница 23: ......
Страница 30: ...Figure 2 Rear View of a Fully Configured AC Powered Services Gateway Chassis 31 ...
Страница 111: ...LEDs 112 ...
Страница 121: ...Port and Interface Numbering 122 ...
Страница 127: ...Port and Interface Numbering 128 ...
Страница 161: ......
Страница 179: ... One SRX5K MPC IOC2 Modular Port Concentrator with two Modular Interface Cards MICs 180 ...
Страница 180: ... One SRX5K 40GE SFP I O card IOC 181 ...
Страница 205: ......
Страница 261: ......
Страница 324: ...c Upload the configuration to RE2 from the USB device 325 ...
Страница 365: ...Figure 143 Installing an SPC 366 ...
Страница 367: ...368 ...
Страница 422: ...5 CHAPTER Troubleshooting Hardware Troubleshooting the SRX5800 425 ...
Страница 423: ......
Страница 457: ......
Страница 473: ...475 ...
Страница 476: ...Restricted Access Area Warning 478 ...
Страница 483: ...485 ...
Страница 496: ...Jewelry Removal Warning 498 ...
Страница 499: ...Operating Temperature Warning 501 ...
Страница 509: ...DC Power Disconnection Warning 511 ...
Страница 513: ...DC Power Wiring Sequence Warning 515 ...
Страница 516: ...DC Power Wiring Terminations Warning 518 ...
Страница 519: ...DC Power Disconnection Warning 521 ...
Страница 523: ...DC Power Wiring Sequence Warning 525 ...
Страница 526: ...DC Power Wiring Terminations Warning 528 ...