www.jps.com.tw
57
10.8 Digital Input Group
Pr.011
DI Status
This parameter shows the DI1 ~ DI16 status by hexadecimal numerical data. Converting this data
to be binary format, status of DI1 ~ DI16 will be presented from LSB to MSB of the data.
For example:
if Pr.011=0
Converting to binary is “0000 0000 0000 0000”. The DI1 ~ DI16 are OFF.
If Pr.011=5
Converting to binary is “0000 0000 0000 0101”. The DI1 and DI3 are ON,and
others are OFF.
Pr.060
DI-x Simulation Inputs
This parameter can be set to a decimal value, and then start the drive The DI startup / shutdown
。
If = 0
Converted to binary is
0000 0000 0000 0000;
Expanded bit by the binary state, you can perform communication:
All of the DI terminal status = OFF
。
If = 5
Converted to binary is
0000 0000 0000 0101
Expanded by the binary bit status, communication execution: DI1 and DI3 state is ON,
the remaining terminals are OFF
。
Pr.061
DI-1 function Select
Pr.062
DI-2 function Select
Pr.063
DI-3 function Select
Pr.064
DI-4 function Select
Pr.065
DI-5 function Select
Pr.066
DI-6 function Select
Pr.067
DI-7 function Select
Pr.068
DI-8 function Select
This parameter group to set the status of the terminal options, if the state of the terminal is
activated, the drive will perform the functions of the action
。
【Note】
The eight belonging 24V-OpenCollector generally optically coupled isolated digital input,
scan execution time is 400us
。
Related options, refer to Chapter 11: Digital input terminal function selection
。
Pr.069
DI-9 function Select
Pr.070
DI-10 function Select
This parameter defaults to two: a special mode of the CUT (DI9) / MARK (DI10), (general standard
mode, do not use)
。
【Note】
The two belong to 5V-OpenCollector fast optical coupler isolated digital input, scan
execution time is 100us
。
Pr.167
DI-11 function Select (FDIX)
Pr.168
DI-12 function Select (FDIY)
This parameter defaults to two: a special mode of the XY tracking input X / Y, (general standard
mode, do not use)
。
【Note】
The two belong to 5V-OpenCollector fast optical coupler isolated digital input, scan
execution time is 100us
。