14.2.3 Torque Mode:Standard Torque Mode:Digital Output
DOx _ Select
018,Driver Torque-Current(%) > Pr.016:Warning Level
DOx _ Select
019,Driver Torque-Current(%) <= Pr.016:Warning Level
When this mode is selected, the drive current is converted to a percentage of the
motor current
G,
Multiplied by Pr.016, as is Comparison value, if the drive is the
actual current> (G x compare value), generate a digital output.
Example:Pr.016=10%,Drive current=6A;Motor current=3A,therefore G=2
When the actual current drive
> (2 x10%),
Generate a digital output
。
【Note】DOx(019)=DOx(018) reverse output。
Pr.016:Torque Compare Level,is
percentage of the motor rated current
setting value comparison
。
DOx _ Select
083,Motor-Torque(%) > Pr.016:Warning Level
DOx _ Select
084,Motor-Torque(%) <= Pr.016:Warning Level
Active when
the motor current to compare the percentage of Pr.016
:Warning Level
If the motor current percentage> Pr.016, generate a digital output
。
【Note】DOx(084)=DOx(083) reverse output。
Pr.016:Torque Compare Level,is
percentage of the motor rated current
setting value comparison
。
Pr.017:I_RMS( % Motor)。