ENGLISH
08.4
SAFETY THERMOSTAT WITH MANUAL RESET
Two safety thermostats are installed on the boiler to read pellet burner and circulating water temperature and trigger to turn off the boiler
when the relevant temperatures are faulty.
The safety thermostats can shutdown the boiler when, for example, the burner overheats, triggering the pellet thermostat, or when there
is no water circulation in the boiler, triggering the water temperature thermostat.
To restore normal boiler operations following forced shutdown by a thermostat, proceed as follows:
1.
Wait until the boiler is completely cold (on average 20
minutes);
2.
Unscrew the thermostat reset button lid on the back of the
boiler (see
F
ig
. 1
, positions
B
or
C
);
3.
Press the button until you hear a CLICK;
4.
Refit the hood;
5.
Reset the alarm from the remote by pressing the button and
waiting for the OFF message;
6.
Start up again the boiler.
If the alarm persists, contact the specialised Technical Service
Center.
PELLET thermostat, to reset alarm AL04 EXHAUST- FAILURE
WATER thermostat, to reset alarm AL19 THERMIC H2O SAFE
Socket unit (
F
ig
. 1
):
A
Electrical socket with bi-polar switch and fuse protection
(see
CHAP.07.4 - ELECTRIC CONNECTIONS
)
B
Pellet burner heat safety thermostat
C
Boiler water heat safety thermostat
D
Room temperature probe
E
External probe socket unit
F
Electronic board programmer connection socket.
F
ig
. 1
A
B
C
D
E
F
49