![Johnson Controls YCIV0157 Скачать руководство пользователя страница 73](http://html1.mh-extra.com/html/johnson-controls/yciv0157/yciv0157_installation-operation-and-maintenance_2023452073.webp)
JOHNSON CONTROLS
73
SECTION 6 - TECHNICAL DATA
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
6
PHYSICAL DATA (SI - STANDARD EFFICIENCY) (CONT'D)
REFRIGERANT R-134A
STANDARD EFFICIENCY
MODEL NUMBER (YCIV____ S/P)
GENERAL UNIT DATA
60HZ
0287
0307
0357
0397
Number of Independent Refrigerant Circuits
3
3
3
3
Refrigerant Charge, R-134a, Ckt.-1/Ckt.-2, kg.
84 / 77 / 77
84 / 84 / 77
84 / 84 / 105
105 / 105 / 105
Oil Charge, Ckt.-1/Ckt.-2, liters
19 / 15 / 15
19 / 19 / 15
19 / 19 / 19
19 / 19 / 19
Glycol Charge (43% concentration), liters
0
0
0
0
Compressors, Semihermetic Screw
Quantity per Chiller
3
3
3
3
Condensers, High Efficiency Fin/Tube with Integral Subcooler
Total Chiller Coil Face Area, m2
35
38
44
49
Number of Rows
3
3
3
3
Fins per meter
669
669
669
669
Condenser Fans
Number, Ckt.-1/Ckt.-2
5/4/4
5/5/4
5/5/6
6/6/6
Low Noise Fans
Fan Motor, HP/kWi
2/1.50
2/1.50
2/1.50
2/1.50
Total Chiller Airflow, l/sec.
79768
85904
98176
110448
Ultra Quiet Fans
Fan Motor, HP/kWi
2/1.50
2/1.50
2/1.50
2/1.50
Total Chiller Airflow, l/sec.
79768
85904
98176
110448
Dual Speed Fans - Normal Speed
Fan, KWi
1.5
1.5
1.5
1.5
Total Chiller, m3/s
67
67
78
78
Dual Speed Fans - Lower Speed
Fan, KWi
1.5
1.5
1.5
1.5
Total Chiller, m3/s
52
52
59
59
High Static Fans
Fan, KWi
3.7
3.7
3.7
3.7
Total Chiller, m3/s
80
86
98
110
Evaporator, Direct Expansion
Water Volume, liters
764.6
893.3
893.3
893.3
Maximum Water Side Pressure, Bar
10
10
10
10
Maximum Refrigerant Side Pressure, Bar
16
16
16
16
Minimum Chilled Water Flow Rate, l/sec.
16
19
19
19
Maximum Chilled Water Flow Rate, l/sec.
76
76
76
76
Water Connections, mm
245
245
245
245
Содержание YCIV0157
Страница 18: ...JOHNSON CONTROLS 18 FORM 201 23 NM2 ISSUE DATE 3 9 2015 SAFETY SYMBOLS THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 104: ...JOHNSON CONTROLS 104 FORM 201 23 NM2 ISSUE DATE 3 9 2015 SECTION 6 TECHNICAL DATA Panel Layout 2 Compressor Models ...
Страница 105: ...JOHNSON CONTROLS 105 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...