TABLE 35 -
COMPRESSOR MOTOR OVERLOAD SETTINGS AND MAX. VSD FREQUENCY (CONT'D)
3 COMP CHILLER MODELS WITH STANDARD (PIN 52 = X) AND ULTRA QUIET FANS (PIN 52 = L)
CHILLER MODEL
(3 COMP)
W/ STD & UQ
FANS
CHILLER NAME-
PLATE VOLTAGE
(VAC)
COMPRESSOR 1
OVERLOAD SET-
TING
(AMPS)
COMPRESSOR 2
OVERLOAD SET-
TING
(AMPS)
COMPRESSOR
3 OVERLOAD
SETTING
(AMPS)
MAXIMUM VSD
FREQUENCY (HZ)
YCIV0267EA/VA
380
289
289
267
182
YCIV0267EA/VA
460
244
244
191
182
YCIV0287EA/VA
380
289
289
289
178
YCIV0287EA/VA
460
242
242
242
178
YCIV0287SA/PA
380
289
289
268
186
YCIV0287SA/PA
460
246
273
192
186
YCIV0307SA/PA
380
289
289
289
188
YCIV0307SA/PA
460
248
248
274
188
YCIV0327EA/VA
380
289
289
289
192
YCIV0327EA/VA
460
250
250
234
192
YCIV0357EA/VA
380
338
338
309
192
YCIV0357EA/VA
460
289
289
232
192
YCIV0357SA/PA
380
331
331
338
200
YCIV0357SA/PA
460
254
254
289
200
YCIV0397SA/PA
380
338
338
338
200
YCIV0397SA/PA
460
289
289
289
200
3 COMP CHILLER MODELS WITH HIGH HEAD/HIGH STATIC FANS (PIN 52 = H)
CHILLER MODEL
(3 COMP)
W/ HH/HS FANS
CHILLER NAME-
PLATE VOLTAGE
(VAC)
COMPRESSOR 1
OVERLOAD SET-
TING
(AMPS)
COMPRESSOR 2
OVERLOAD SET-
TING
(AMPS)
COMPRESSOR 3
OVERLOAD SET-
TING
(AMPS)
MAXIMUM VSD
FREQUENCY
(HZ)
YCIV0267EA/VA
380
289
289
267
182
YCIV0267EA/VA
460
244
244
191
182
YCIV0287EA/VA
380
289
289
289
178
YCIV0287EA/VA
460
242
242
242
178
YCIV0287SA/PA
380
289
289
268
186
YCIV0287SA/PA
460
246
273
192
186
YCIV0307SA/PA
380
289
289
289
188
YCIV0307SA/PA
460
248
248
274
188
YCIV0327EA/VA
380
289
289
289
192
YCIV0327EA/VA
460
250
250
234
192
YCIV0357EA/VA
380
338
338
309
192
YCIV0357EA/VA
460
289
289
232
192
YCIV0357SA/PA
380
331
331
338
200
YCIV0357SA/PA
460
254
254
289
200
YCIV0397SA/PA
380
338
338
338
200
YCIV0397SA/PA
460
289
289
289
200
NOTE: Overload settings are based on Chiller Model and Condenser Fan Option
Содержание YCIV0157
Страница 18: ...JOHNSON CONTROLS 18 FORM 201 23 NM2 ISSUE DATE 3 9 2015 SAFETY SYMBOLS THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 104: ...JOHNSON CONTROLS 104 FORM 201 23 NM2 ISSUE DATE 3 9 2015 SECTION 6 TECHNICAL DATA Panel Layout 2 Compressor Models ...
Страница 105: ...JOHNSON CONTROLS 105 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...