![Johnson Controls YCIV0157 Скачать руководство пользователя страница 272](http://html1.mh-extra.com/html/johnson-controls/yciv0157/yciv0157_installation-operation-and-maintenance_2023452272.webp)
JOHNSON CONTROLS
272
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
SECTION 8 - MICROPANEL
OPTIONS KEY
LD10605
OPTIONS
KEY
Options Key Operation
The OPTIONS key provides the user with a display of
unit configuration and the capability to modify the con-
figuration. These options can only be viewed under the
OPTIONS key. To view the current options settings,
press the OPTIONS key. Each press of the OPTIONS
key or press of the ▲ or ▼ (
ARROW) keys will scroll
to the next option setting. The ◄ and ► (
ARROW)
keys allow changing the option choices. The
(EN-
TER) key must be pressed after a selection is made to
save the change in memory.
An explanation of each option message is provided be-
low.
Display Language Selection
The display language can be selected for English,
Dutch, German, Italian, and Chinese
OPTIONS DISPLAY LANGUAGE
◄ ► XXXXXXXXXXXXXXXXXX
The default language will be English.
Chilled Liquid Cooling Mode Selection
The Chilled liquid cooling mode can be selected for
Water Cooling or low temperature Glycol Cooling.
OPTIONS CHILLED LIQUID COOLING MODE
◄ ► XXXXXXXXXXXXXXXXXX
When Water Cooling is chosen, the chilled liquid tem-
perature setpoint can only be programmed from 40°F
to 70°F
OPTIONS CHILLED LIQUID COOLING MODE
◄ ► WATER COOLING
When Glycol Cooling is chosen, the chilled liquid
temperature setpoint can be programmed from 10°F to
70°F.
OPTIONS CHILLED LIQUID COOLING MODE
◄ ► GLYCOL COOLING
The default Chilled Liquid Mode will be WATER.
Содержание YCIV0157
Страница 18: ...JOHNSON CONTROLS 18 FORM 201 23 NM2 ISSUE DATE 3 9 2015 SAFETY SYMBOLS THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 104: ...JOHNSON CONTROLS 104 FORM 201 23 NM2 ISSUE DATE 3 9 2015 SECTION 6 TECHNICAL DATA Panel Layout 2 Compressor Models ...
Страница 105: ...JOHNSON CONTROLS 105 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...