JOHNSON CONTROLS
49
SECTION 4 - INSTALLATION
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
4
VOLTS FREE CONTACTS
Voltage free contacts are rated at 115VAC, 100VA re-
sistive load only. Inductive loads must be suppressed
across the coil.
Chilled Liquid Pump Starter
Terminals 23 and 24 on 1TB close to start the chilled
liquid pump. This contact can be used as a master start/
stop for the pump in conjunction with the daily start/
stop schedule. Cycle the pumps from the unit panel if
the unit will be operational or shut-down during sub-
freezing conditions. Refer to the
for more information on testing
the pumps
.
Run Contact
Terminals 21 and 22 on 1TB (
and
) close to indicate that a
system is running.
Alarm Contacts
The Systems 1/3 and 2/4 each have a single voltage-
free contact, which will operate to signal an alarm
condition whenever any system locks out, or there is a
power failure. To obtain system alarm signal, connect
the alarm circuit to volt free Terminals 25 and 26 (Sys
1/3), Terminals 27 and 28 (Sys 2/4) of 1TB (
).
SYSTEM INPUTS
Flow Switch
A chilled liquid flow switch of suitable type MUST be
connected between Terminals 2 and 13 of 1TB (
) to pro-
vide protection against loss of liquid flow, which will
cause evaporator freeze-up if the chiller is permitted
to run. The flow switch circuitry is a 115VAC circuit.
Contacts must be rated for low current (10ma). Gold
contacts should be used.
Remote Run / Stop
A Remote Run/Stop input is available for each pair of
systems (1/3 and 2/4). These inputs require a dry con-
tact to start and stop the system. System 1/3 remote
dry contacts are connected between Terminals 2 and
and
) and System 2/4 dry contacts are connected
between Terminals 2 and 16 of 1TB (
). If remote start/stop
is not utilized, a jumper must be paced across the ter-
minals to allow the system to run. The remote run/stop
circuitry is a 115VAC circuit. Contacts must be rated
for low current (10ma). Gold contacts should be used.
Remote Print
Closure of suitable contacts connected to Terminals 2
and
) will cause a hard copy printout of
Operating Data/Fault History to be made if an optional
printer is connected to the RS-232 port. The remote
print circuitry is a 115VAC circuit. Contacts must be
rated for low current (10ma). Gold contacts should be
used.
Optional Remote Setpoint Offset –
Temperature
A current or voltage signal connected to Terminals
17 and 18 will provide a remote offset function of the
chilled liquid setpoint, if required. See
for the input
for a description of the option.
Optional Remote Setpoint Offset – Current
A current or voltage signal connected to Terminals 19
and 20 will provide remote setting of the current limit
setpoint, if required. See
and
for a description of the option.
Optional Remote Setpoint Offset – Sound
Limiting
A current or voltage signal connected to Terminals
40 and 41will provide remote setting of sound limit
setpoint, if required. See
and
Содержание YCIV0157
Страница 18: ...JOHNSON CONTROLS 18 FORM 201 23 NM2 ISSUE DATE 3 9 2015 SAFETY SYMBOLS THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 104: ...JOHNSON CONTROLS 104 FORM 201 23 NM2 ISSUE DATE 3 9 2015 SECTION 6 TECHNICAL DATA Panel Layout 2 Compressor Models ...
Страница 105: ...JOHNSON CONTROLS 105 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...