background image

TEC2104-3 N2 Networked Multi-Stage Economizer Thermostat Installation Instructions

6

The Controller Point Type is the fixed-point definition 
inside the controller. The BAS Model Point type is the 
definition inside the model file. Use an NCM Control 
System object to retrieve the data.

The most recent N2 command received by any of the 
N2 Bus Objects listed in Table 1 controls the 
thermostat.

If an Analog Data (AD) object is overridden by the 
Metasys system, all local changes attempted through 
the thermostat keypad for that AD object are ignored 
until the override is released. For example, if the 
Metasys system sends a write command to turn 
System Mode Off, and then the occupant selects 
System Mode On at the TEC keypad, the TEC ends up 
with the System Mode On; however, if the Metasys 
system sends an override command to turn System 
Mode Off, and then the occupant selects System Mode 
On at the TEC keypad, the TEC keeps the System 
Mode Off.

Once an override is released, the AD object may once 
again be changed through the thermostat keypad, but 
the thermostat does not retain any data entered at the 
TEC keypad during the override.

The value for Heating SP (ADI-3) and Setback 
Heating SP (ADI-5) must stay within the limits 
established in the controller by Minimum Heat SP 
(ADI-7 read-only) and Maximum Heat SP (ADI-8).

The value for Cooling SP (ADI-4) and Setback 
Cooling SP (ADI-6) must stay within the limits 
established in the controller by Minimum Cool SP 
(ADI-9) and Maximum Cool SP (ADI-10 read-only).

If a setpoint is overridden, the TEC, if necessary, 
adjusts the other setpoint to maintain the minimum 
deadband between the setpoints. The setpoints can be 
spread further apart but can never be adjusted closer 
than the current minimum deadband value.

Failure to stay within the limits for a command results in 
an N2 Negative Acknowledge (NAK) error from the 
TEC2104-3 thermostat.

Overrides take precedence over any local adjustment 
or command in the TEC2104-3 thermostat.

You must not have a Relinquish Default for the 
setpoints if you want to change them from the 
thermostat display.

If there is a Relinquish Default for the setpoints, the 
Network Automation Engine (NAE) always has an 
Override for either an adjusted value or the Relinquish 
Default Value. You should use Operator Override and 
Release Operator Override if you want to command the 
setpoint and release it to local control.

Once all the NAE commands are released, the 
Override Status in the Hardware tab should be False. 
At that time, the user should be able to change the 
setpoint from the local display.

All overrides are released automatically after 
10 minutes of no communications (for example, 
network cable is removed from the TEC, causing loss 
of network communications).

Temp Alarm

6

BI-2

N2 BI

CSBI

0 = Normal
1 = Alarm

DI2

6,7

BI-3

N2 BI

CSBI

0 = Off
1 = On

1.

Commandable.

2.

If one setpoint is overridden, the other setpoint may be automatically overridden by the TEC2104-3 thermostat to maintain 
the minimum deadband between the two setpoints.

3.

The Multiple Command Output (MCO) object is used to schedule multiple Multi-State Objects (MSOs).

4.

When defining the N2 MSO, select TEC Mode from the States Text Menu. Type 4 for the TEC2104-3 thermostat.

5.

On the Metasys Network Command Module (NCM) system, map BD-9 

Temp Units Mode

 as a Binary Output (BO) object 

with Auto Restore and Local Control set.

6.

Can be a Change-of-State (COS) alarm to the BAS or N2 Dialer Module (NDM) to initiate a dial-out.

7.

The state of DI1 and DI2 is communicated over the N2 network even if the digital inputs are configured as 

None

 through 

the local interface at the thermostat.

Table 1:  N2 Bus Objects  (Part 2 of 2)

Point Name

TEC Point 
Type/Address

N30/NAE 
Object Type

BAS Model 
Point Type

Override Range

Содержание TEC2104-3

Страница 1: ...injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or a...

Страница 2: ...he thermostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors incl...

Страница 3: ...ANT Make all wiring connections in accordance with local national and regional regulations Do not exceed the electrical ratings of the TEC2104 3 Thermostat Figure 5 Wiring the TEC2104 3 Thermostat 24...

Страница 4: ...etpoint if necessary to maintain the minimum deadband between the two setpoints The setpoints can be spread farther apart but can never be adjusted closer than 2F 1C apart If a supervisory controller...

Страница 5: ...m Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP1 ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP1 ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP ADI 10 N2 AI CSAD 100 F 37 5 C...

Страница 6: ...ithin the limits for a command results in an N2 Negative Acknowledge NAK error from the TEC2104 3 thermostat Overrides take precedence over any local adjustment or command in the TEC2104 3 thermostat...

Страница 7: ...o activate a setpoint adjustment Backlit Liquid Crystal Display LCD The TEC2104 3 Thermostat includes a 2 line 8 character backlit display Low level backlighting is present during normal operation and...

Страница 8: ...the YES key at the exit prompt To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for approximately 8 seconds...

Страница 9: ...cess No Access No Access Temporary Temperature Setpoints Access Access No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Pwr del1 Sets the delay time...

Страница 10: ...er a heating or cooling cycle has ended The fan delay is only active when the fan is in the Auto mode Com addr N2 network address at the thermostat coincides with the address assigned at the superviso...

Страница 11: ...n o n c Contact open Occupied contact closed Unoccupied n o Contact closed Occupied contact open Unoccupied The contact toggles with the internal Occupied Unoccupied schedule or the NSB contact on on...

Страница 12: ...er Resuming the Programmed Schedule This menu only appears when the thermostat is in the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts u...

Страница 13: ...Thermostat Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt appears on the disp...

Страница 14: ...ccupied and unoccupied states Smart Fan Mode smart Energizes the fan all the time for occupied states and only on a call for heating or cooling in unoccupied states This is the default setting To sele...

Страница 15: ...more controllers have the same address Change each duplicate address to a unique number The N2 Bus contains too many devices Do not exceed the maximum number of devices allowed on the N2 Bus per super...

Страница 16: ...acklit Display 40 0 F 40 0 C to 122 0 F 50 0 C in 0 5 Increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F...

Отзывы: