TEC2104-3 N2 Networked Multi-Stage Economizer Thermostat Installation Instructions
5
Table 1: N2 Bus Objects (Part 1 of 2)
Point Name
TEC Point
Type/Address
N30/NAE
Object Type
BAS Model
Point Type
Override Range
Room Temp
1
ADI-1
N2 AI
CSAD
32 to 122°F (0 to 50°C)
Aux Temp/Outdoor Temp
ADI-2
N2 AI
CSAD
-40 to 122°F (-40 to 50°C)
Heating SP
(Occupied Heating SP)
ADI-3
N2 AO
CSAD
40 to 90°F (4.5 to 32°C)
Cooling SP
(Occupied Cooling SP)
ADI-4
N2 AO
CSAD
54 to 100°F (12 to 37.5°C)
Setback Heating SP
(Unoccupied Heating SP)
ADI-5
N2 AO
CSAD
40 to 90°F (4.5 to 32°C)
Setback Cooling SP
(Unoccupied Cooling SP)
ADI-6
N2 AO
CSAD
54 to 100°F (12 to 37.5°C)
Minimum Heat SP
ADI-7
N2 AI
CSAD
40°F (4.5°C)
Maximum Heat SP
ADI-8
N2 AO
CSAD
40 to 90°F (4.5 to 32°C)
Minimum Cool SP
ADI-9
N2 AO
CSAD
54 to 100°F (12 to 37.5°C)
Maximum Cool SP
ADI-10
N2 AI
CSAD
100°F (37.5°C)
Mixed Air/Discharge Air
Temperature (MS)
ADI-11
N2 AI
CSAD
-40 to 122°F (-40 to 50°C)
Fan
BD-1
N2 BO
CSBD
0 = Auto
1 = On
Mode
BD-2
N2 MSO
3
,
4
CSMS
0 = Off
1 = Cool
2 = Heat
3 = Auto
Occupancy
BD-3
N2 BO
CSBD
0 = Unoccupied
1 = Occupied
W1 State
BD-4
N2 BI
CSBD
0 = Off
1 = On
W2 State
BD-5
N2 BI
CSBD
0 = Off
1 = On
Y1 State
BD-6
N2 BI
CSBD
0 = Off
1 = On
Y2 State
BD-7
N2 BI
CSBD
0 = Off
1 = On
G State - Fan
BD-8
N2 BI
CSBD
0 = Off
1 = On
Temp Units
(Local Display Only)
BD-9
N2 BO
See Footnote 5.
0 = °C
1 = °F
Occupancy Override
BD-10
N2 BI
CSBD
0 = No Override
1 = Override
Temporary Occupancy
Time
BD-11
N2-MSO
CSMS
0 = 0 hours
1 = 1 hour
2 = 2 hours
.
.
12 = 12 hours
DI1
6,7
BI-1
N2 BI
CSBI
0 = Off
1 = On