TEC2104-3 N2 Networked Multi-Stage Economizer Thermostat Installation Instructions

12

Operation

Programming/Operating the TEC2104-3 
Thermostat

Once the thermostat is configured via the Installer 
Configuration Menu, its operating parameters can be 
programmed via the Main User Menu. Access this 
menu by pressing the 

MENU

 key during normal 

thermostat operation. The Main User Menu contains 
the basic operating features of the thermostat.

The Main User Menu also uses Auto Help, which is 
displayed automatically in the menu when there is a 
pause in programming activity. To exit Auto Help, 
continue with the programming selection. When the 
thermostat is in the Main User Menu and is left 
unattended for 45 seconds, the menu reverts to the 
Status Display Menu.

Enabling Override Schedule

Note:

Enabling Override Schedule only appears when 

in the Unoccupied Mode.

The override schedule prompt only appears when the 
thermostat is in the unoccupied state. This menu 
selection gives the user the option of overriding the 
unoccupied setpoints with the occupied setpoints for 
the amount of time specified under the 

TOccTime

 

parameter. See the 

Configuring the TEC2104-3 

Thermostat

 section.

Note:

If one of the digital inputs is configured to 

operate as a remote override contact, this menu is 
disabled.

To override the unoccupied state while in the Main 
User Menu:

1.

Press the 

NO

 key to all prompts until the Cancel 

ovrd prompt appears. If the thermostat is in the 
unoccupied state, this is the first prompt.

2.

Press the 

YES

 key to enable the temporary 

override. The thermostat returns to the Status 
Display Menu.

When scrolling through the Status Display Menu, 
Override now appears for the occupancy status 
parameter.

Resuming the Programmed Schedule

This menu only appears when the thermostat is in the 
unoccupied override mode.

To resume the schedule while in the Main User Menu:

1.

Press the 

NO

 key to all prompts until the Cancel 

ovrd Y/N prompt appears. If the thermostat is in the 
unoccupied override state, this is the first prompt.

2.

Press the 

YES

 key to resume the programmed 

schedule.

The thermostat returns to the Status Display Menu.

C mech

Determines whether to allow 
mechanical cooling (compressor 
operation) if free cooling 
(economizer operation) cannot 
maintain the cooling setpoint.
Default: 

off

(on):

 Typically applies when the Mixed air Sensor (MS) is installed 

before the mechanical cooling refrigeration coils in the mixing 
plenum. In this scenario, mechanical cooling is allowed when free 
cooling cannot maintain the cooling setpoint.

(off):

 Typically applies when the remote MS is installed after the 

mechanical cooling refrigeration coils. In this scenario, mechanical 
cooling will never operate at the same time as free cooling.

Mix stpt

2

Establishes the mixed air 
temperature when operating in the 
economizer mode.
Default: 

55.0°F/13.0°C

Range: 

50.0°F/10.0°C

 to 

90.0°/32.0°C

MS temp

Displays the mixed air temperature. 
Requires that an MS be installed 
and connected.
Default: 

N/A

The mixed air temperature can be used to help service and 
troubleshoot the equipment and the economizer operation. 

1.

When adjusting the numeric value, press the 

UP

 or 

DOWN

 arrow key to change the value by single increments; press and 

hold the 

UP

 or 

DOWN

 arrow key to change the numeric value in increments of ten.

2.

When adjusting the temperature, press the 

UP

 or 

DOWN

 arrow key to change the value in 0.5F°/0.5C° increments; press 

and hold the 

UP

 or 

DOWN

 arrow key to change the value in 5.0F°/5.0C° increments.

Table 2:  Installer Configuration Menu  (Part 5 of 5)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание TEC2104-3

Страница 1: ...injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or a...

Страница 2: ...he thermostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors incl...

Страница 3: ...ANT Make all wiring connections in accordance with local national and regional regulations Do not exceed the electrical ratings of the TEC2104 3 Thermostat Figure 5 Wiring the TEC2104 3 Thermostat 24...

Страница 4: ...etpoint if necessary to maintain the minimum deadband between the two setpoints The setpoints can be spread farther apart but can never be adjusted closer than 2F 1C apart If a supervisory controller...

Страница 5: ...m Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP1 ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP1 ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP ADI 10 N2 AI CSAD 100 F 37 5 C...

Страница 6: ...ithin the limits for a command results in an N2 Negative Acknowledge NAK error from the TEC2104 3 thermostat Overrides take precedence over any local adjustment or command in the TEC2104 3 thermostat...

Страница 7: ...o activate a setpoint adjustment Backlit Liquid Crystal Display LCD The TEC2104 3 Thermostat includes a 2 line 8 character backlit display Low level backlighting is present during normal operation and...

Страница 8: ...the YES key at the exit prompt To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for approximately 8 seconds...

Страница 9: ...cess No Access No Access Temporary Temperature Setpoints Access Access No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Pwr del1 Sets the delay time...

Страница 10: ...er a heating or cooling cycle has ended The fan delay is only active when the fan is in the Auto mode Com addr N2 network address at the thermostat coincides with the address assigned at the superviso...

Страница 11: ...n o n c Contact open Occupied contact closed Unoccupied n o Contact closed Occupied contact open Unoccupied The contact toggles with the internal Occupied Unoccupied schedule or the NSB contact on on...

Страница 12: ...er Resuming the Programmed Schedule This menu only appears when the thermostat is in the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts u...

Страница 13: ...Thermostat Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt appears on the disp...

Страница 14: ...ccupied and unoccupied states Smart Fan Mode smart Energizes the fan all the time for occupied states and only on a call for heating or cooling in unoccupied states This is the default setting To sele...

Страница 15: ...more controllers have the same address Change each duplicate address to a unique number The N2 Bus contains too many devices Do not exceed the maximum number of devices allowed on the N2 Bus per super...

Страница 16: ...acklit Display 40 0 F 40 0 C to 122 0 F 50 0 C in 0 5 Increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F...

Отзывы: