TEC2104-3 N2 Networked Multi-Stage Economizer Thermostat Installation Instructions

8

Applicable Alarms – The backlight lights up as an 
alarm condition is displayed.

Note:

Press the 

YES/SCROLL

 key to temporarily stop 

this menu from scrolling.

The 

Main User Menu

 is used to access and change 

the basic operating parameters of the thermostat. 
Access this menu by pressing the 

MENU

 key during 

normal thermostat operation.

The 

Installer Configuration Menu

 is used to set up 

the thermostat for application-specific operation. To 
access this menu, press and hold the 

MENU

 key for 

approximately 8 seconds.

Configuring the TEC2104-3 Thermostat

The TEC2104-3 Thermostat comes from the factory 
with default settings for all configurable parameters. 
The default settings are shown in Table 2. T
reconfigure the parameters via the thermostat, follow 
these steps:

1.

To access the Installer Configuration Menu, press 
and hold the 

MENU

 key for approximately 

8 seconds.

2.

Once the Installer Configuration Menu begins, 
press the 

NO

key to scroll through the parameters 

listed in Table 2.

3.

When the desired parameter is displayed, use the 

YES

 key to choose the desired selection option.

4.

Press the 

YES

 key and then the 

NO

 key to 

continue scrolling through the parameters.

To exit the Installer Configuration Menu at any time, 
press the 

MENU

 key and press the 

YES

 key at the exit 

prompt. To pass over a parameter without changing it, 
press the 

NO

 key.

When the thermostat is in the Installer Configuration 
Menu and left unattended for approximately 8 seconds, 
the thermostat reverts to the Status Display Menu.

Configuring Inputs DI1 and DI2

When DI1 and DI2 are configured for an alarm 
condition, an alarm condition is displayed locally when 
the input is closed. An alarm message is included on 
the scrolling Status Display Menu and when the 
message is displayed, the backlight momentarily 
lights up.

Both inputs can be configured to the Selection Options 
included in Table 2. 

Table 2:  Installer Configuration Menu  (Part 1 of 5)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

DI1

Configuration of Digital Input 1.
Default: 

None

(None):

 No function is associated with an input.

(Service): 

A Service alarm is displayed on the thermostat when the 

input is energized. This input can be tied into the air conditioning 
unit control card, which provides an alarm should there be a 
malfunction.

(Filter):

 A Filter alarm is displayed. This alarm can be connected to 

a differential pressure switch that monitors a filter.

(RemOVR):

 Temporary occupancy request via a remote input. This 

override function is controlled by a manual remote occupancy 
override. When enabled, this condition disables the override 
capability of the thermostat.

(RemNSB):

 Remote Night Setback (NSB) via a time clock input, an 

occupancy sensor, or from a voltage-free contact. 
Contact open = Occupied; contact closed = Unoccupied.

Содержание TEC2104-3

Страница 1: ...injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or a...

Страница 2: ...he thermostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors incl...

Страница 3: ...ANT Make all wiring connections in accordance with local national and regional regulations Do not exceed the electrical ratings of the TEC2104 3 Thermostat Figure 5 Wiring the TEC2104 3 Thermostat 24...

Страница 4: ...etpoint if necessary to maintain the minimum deadband between the two setpoints The setpoints can be spread farther apart but can never be adjusted closer than 2F 1C apart If a supervisory controller...

Страница 5: ...m Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP1 ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP1 ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP ADI 10 N2 AI CSAD 100 F 37 5 C...

Страница 6: ...ithin the limits for a command results in an N2 Negative Acknowledge NAK error from the TEC2104 3 thermostat Overrides take precedence over any local adjustment or command in the TEC2104 3 thermostat...

Страница 7: ...o activate a setpoint adjustment Backlit Liquid Crystal Display LCD The TEC2104 3 Thermostat includes a 2 line 8 character backlit display Low level backlighting is present during normal operation and...

Страница 8: ...the YES key at the exit prompt To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for approximately 8 seconds...

Страница 9: ...cess No Access No Access Temporary Temperature Setpoints Access Access No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Pwr del1 Sets the delay time...

Страница 10: ...er a heating or cooling cycle has ended The fan delay is only active when the fan is in the Auto mode Com addr N2 network address at the thermostat coincides with the address assigned at the superviso...

Страница 11: ...n o n c Contact open Occupied contact closed Unoccupied n o Contact closed Occupied contact open Unoccupied The contact toggles with the internal Occupied Unoccupied schedule or the NSB contact on on...

Страница 12: ...er Resuming the Programmed Schedule This menu only appears when the thermostat is in the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts u...

Страница 13: ...Thermostat Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt appears on the disp...

Страница 14: ...ccupied and unoccupied states Smart Fan Mode smart Energizes the fan all the time for occupied states and only on a call for heating or cooling in unoccupied states This is the default setting To sele...

Страница 15: ...more controllers have the same address Change each duplicate address to a unique number The N2 Bus contains too many devices Do not exceed the maximum number of devices allowed on the N2 Bus per super...

Страница 16: ...acklit Display 40 0 F 40 0 C to 122 0 F 50 0 C in 0 5 Increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F...

Отзывы: