TEC2104-3 N2 Networked Multi-Stage Economizer Thermostat Installation Instructions

4

Connecting the N2 Bus

To connect the N2 Bus:

1.

Set the N2 address of the TEC2104-3 Thermostat 
per the engineering drawings prior to wiring the 
thermostat. (See the 

Com addr

 parameter in 

Table 2 to set the N2 address for the thermostat.) 
Also test for N2 voltage, polarity, and isolation prior 
to wiring the thermostat.

2.

Observe the polarity when connecting the N2 Bus 
wires to the thermostat.

3.

After the N2 Bus wires are connected to the first 
thermostat, continue in a daisy-chained fashion to 
the next thermostat.

Note:

The thermostat N2 Bus is self-terminating. The 

N2 Bus wiring must be twisted-pair lines. Do not run 
the N2 Bus wiring in the same conduit as line voltage 
wiring (30 VAC or above) or other wiring that switches 
power to highly inductive loads (such as contactors, 
coils, motors, or generators).

For more N2 Bus overview information, refer to the 

N2 

Communications Bus Technical Bulletin (LIT-636018)

 

and the 

ASC and N2 Bus Networking and 

Troubleshooting Guide (LIT-6363003)

.

N2 Device Mapping

Define the TEC2104-3 Thermostat as a Vendor Device 
(VND) when adding the thermostat to the supervisory 
controller.

The Thermostat Point (Type/Address) is the fixed-point 
definition inside the thermostat. The most recent N2 
command received by any of the Object Types listed in 
Table 1 controls the thermostat.

Overrides take priority over any local adjustment or 
command in the thermostat.

If a setpoint is overridden, the thermostat adjusts the 
other setpoint, if necessary, to maintain the minimum 
deadband between the two setpoints. The setpoints 
can be spread farther apart, but can never be adjusted 
closer than 2F°/1C° apart.

If a supervisory controller commands an override of an 
analog or binary object, all local changes attempted 
through the thermostat keypad for that object are 
ignored until the override is released. For example, if 
the supervisory controller sends an override message 
to turn System Mode Off, and then the user selects 
System Mode On at the thermostat keypad, the 
thermostat keeps the System Mode Off.

When an override is released, the object may once 
again be changed through the thermostat keypad, but 
the thermostat does not retain any data entered at the 
thermostat keypad during the override.

All overrides are released automatically after 
10 minutes of no communications (for example, if the 
network cable is removed from the thermostat, causing 
a loss of network communications).

Metasys® System Person-Machine Interface (PMI)

Do not direct-map any points; instead, run control of 
these points through the Control System (CS) object. 
The supervisory controller Model Point Type is the 
definition inside the model file. Use a CS object to 
retrieve the data.

Metasys System Extended Architecture

There must not be a Relinquish Default for the 
setpoints if you desire to change them from the 
thermostat display. If there is a Relinquish Default for 
the setpoints, the supervisory controller always has an 
Override for either an Adjusted value or the Relinquish 
Default value. Use the Operator Override and the 
Release Operator Override to command the setpoint 
and release it to local control. At that time, the user is 
able to change the setpoint from the local display.

Содержание TEC2104-3

Страница 1: ...injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or a...

Страница 2: ...he thermostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors incl...

Страница 3: ...ANT Make all wiring connections in accordance with local national and regional regulations Do not exceed the electrical ratings of the TEC2104 3 Thermostat Figure 5 Wiring the TEC2104 3 Thermostat 24...

Страница 4: ...etpoint if necessary to maintain the minimum deadband between the two setpoints The setpoints can be spread farther apart but can never be adjusted closer than 2F 1C apart If a supervisory controller...

Страница 5: ...m Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP1 ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP1 ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP ADI 10 N2 AI CSAD 100 F 37 5 C...

Страница 6: ...ithin the limits for a command results in an N2 Negative Acknowledge NAK error from the TEC2104 3 thermostat Overrides take precedence over any local adjustment or command in the TEC2104 3 thermostat...

Страница 7: ...o activate a setpoint adjustment Backlit Liquid Crystal Display LCD The TEC2104 3 Thermostat includes a 2 line 8 character backlit display Low level backlighting is present during normal operation and...

Страница 8: ...the YES key at the exit prompt To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for approximately 8 seconds...

Страница 9: ...cess No Access No Access Temporary Temperature Setpoints Access Access No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Pwr del1 Sets the delay time...

Страница 10: ...er a heating or cooling cycle has ended The fan delay is only active when the fan is in the Auto mode Com addr N2 network address at the thermostat coincides with the address assigned at the superviso...

Страница 11: ...n o n c Contact open Occupied contact closed Unoccupied n o Contact closed Occupied contact open Unoccupied The contact toggles with the internal Occupied Unoccupied schedule or the NSB contact on on...

Страница 12: ...er Resuming the Programmed Schedule This menu only appears when the thermostat is in the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts u...

Страница 13: ...Thermostat Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt appears on the disp...

Страница 14: ...ccupied and unoccupied states Smart Fan Mode smart Energizes the fan all the time for occupied states and only on a call for heating or cooling in unoccupied states This is the default setting To sele...

Страница 15: ...more controllers have the same address Change each duplicate address to a unique number The N2 Bus contains too many devices Do not exceed the maximum number of devices allowed on the N2 Bus per super...

Страница 16: ...acklit Display 40 0 F 40 0 C to 122 0 F 50 0 C in 0 5 Increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F...

Отзывы: