Entering Permanent Temperature Setpoints

The first prompt appearing in the Main User Menu of 
the thermostat when in the occupied state is to set the 
permanent temperature setpoint.

To enter the permanent heating and cooling setpoints 
for the Occupied and Unoccupied Modes, follow the 
steps in Table 3. When changing the temperatures, 
press the keys once to change the temperature in 
0.5F°/0.5C° increments; press and hold down the keys 
to change the temperature in 5.0F°/5.0C° increments. 

Entering Temporary Temperature Setpoints

To temporarily change the setpoint, press the 

UP/DOWN

 arrow keys to change the temporary 

setpoint for the current mode of operation.

Note:

Whether the thermostat is heating or cooling, 

the respective setpoint is temporarily adjusted. To 
toggle between the temporary heating and cooling 
setpoints, press the 

NO

 key while changing the 

temporary setpoints.

Ending Temporary Temperature Setpoints

The temporary setpoints remain in effect for the 
duration set in the 

TOccTime

 parameter or until 

manually released.

To release the temporary setpoint sooner, while in the 
Main User Menu:

1.

Press the 

YES

 key to the first prompt that appears.

2.

If the thermostat does not immediately return to the 
Status Display Menu, press the 

MENU

 key again 

and press the 

YES

 key to exit the Main User Menu.

The setpoint reverts to the Permanent Temperature 
Setpoint.

Selecting the System Mode

The thermostat has four system modes:

Table 3:  Entering Permanent Temperature 

Setpoints (Part 1 of 2)

Thermostat 
Display

Description

Press the 

MENU

 key while in the 

Status Display Menu to enter the 
Main User Menu.

Press the 

NO

 key to all prompts until 

the temperature setpoint prompt 
appears on the display (it may be the 
first prompt). Press the 

YES

 key to 

enter the temperature setting menu.

Press the 

YES

 key to change the 

occupied cooling setpoint. Press the 

NO

 key to advance to the occupied 

heating setpoint menu.

Press the 

UP/DOWN

 arrow keys to 

set the temperature. Press the 

YES

 

key to store the value and advance to 
the next menu.

Press the 

YES

 key to change the 

occupied heating setpoint. Press the 

NO

 key to advance to the unoccupied 

cooling setpoint menu.

Press the 

UP/DOWN

 arrow keys to 

set the temperature. Press the 

YES

 

key to store the value and advance to 
the next menu.

Press the 

YES

 key to change the 

unoccupied cooling setpoint. Press 
the 

NO

 key to advance to the 

unoccupied heating setpoint.

Press the 

UP/DOWN

 arrow keys to 

set the temperature. Press the 

YES

 

key to store the value and advance to 
the next menu.

RoomTemp 
75.0

°

Temperat 
set? Y/N 

Cooling 
set? Y/N 

Cooling 
75.0

°

Heating 
set? Y/N 

Heating 
68.0

°

Unocc CL 
set? Y/N

 

Unocc CL 
80.0

°

Press the 

YES

 key to change the 

unoccupied heating setpoint. Press 
the 

NO

 key to advance to the 

temperature display units.

Press the 

UP/DOWN

 arrow keys to 

set the temperature. Press the 

YES

 

key to store the value and advance to 
the next menu.

Press the 

YES

 key to set the display 

units to °F or °C. Press the 

NO

 key to 

advance to the temperature setpoint 
type menu.

Press the 

YES

 key to return to the 

Status Display Menu or press the 

NO

 

key to reenter the temperature 
setting menu.

Table 3:  Entering Permanent Temperature 

Setpoints (Part 2 of 2)

Thermostat 
Display

Description

Unocc HT
set? Y/N 

Unocc HT
62.0

°

F

 

°

F/

°

set? Y/N 

Exit?
 Y/N 

Содержание TEC2104-3

Страница 1: ...injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or a...

Страница 2: ...he thermostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors incl...

Страница 3: ...ANT Make all wiring connections in accordance with local national and regional regulations Do not exceed the electrical ratings of the TEC2104 3 Thermostat Figure 5 Wiring the TEC2104 3 Thermostat 24...

Страница 4: ...etpoint if necessary to maintain the minimum deadband between the two setpoints The setpoints can be spread farther apart but can never be adjusted closer than 2F 1C apart If a supervisory controller...

Страница 5: ...m Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP1 ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP1 ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP ADI 10 N2 AI CSAD 100 F 37 5 C...

Страница 6: ...ithin the limits for a command results in an N2 Negative Acknowledge NAK error from the TEC2104 3 thermostat Overrides take precedence over any local adjustment or command in the TEC2104 3 thermostat...

Страница 7: ...o activate a setpoint adjustment Backlit Liquid Crystal Display LCD The TEC2104 3 Thermostat includes a 2 line 8 character backlit display Low level backlighting is present during normal operation and...

Страница 8: ...the YES key at the exit prompt To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for approximately 8 seconds...

Страница 9: ...cess No Access No Access Temporary Temperature Setpoints Access Access No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Pwr del1 Sets the delay time...

Страница 10: ...er a heating or cooling cycle has ended The fan delay is only active when the fan is in the Auto mode Com addr N2 network address at the thermostat coincides with the address assigned at the superviso...

Страница 11: ...n o n c Contact open Occupied contact closed Unoccupied n o Contact closed Occupied contact open Unoccupied The contact toggles with the internal Occupied Unoccupied schedule or the NSB contact on on...

Страница 12: ...er Resuming the Programmed Schedule This menu only appears when the thermostat is in the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts u...

Страница 13: ...Thermostat Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt appears on the disp...

Страница 14: ...ccupied and unoccupied states Smart Fan Mode smart Energizes the fan all the time for occupied states and only on a call for heating or cooling in unoccupied states This is the default setting To sele...

Страница 15: ...more controllers have the same address Change each duplicate address to a unique number The N2 Bus contains too many devices Do not exceed the maximum number of devices allowed on the N2 Bus per super...

Страница 16: ...acklit Display 40 0 F 40 0 C to 122 0 F 50 0 C in 0 5 Increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F...

Отзывы: