TEC2104-3 N2 Networked Multi-Stage Economizer Thermostat Installation Instructions 

15

Repair Information

If the TEC2104-3 Thermostat fails to operate within its 
specifications, see Table 5 for troubleshooting details 
and Table 6 for alarm messaging. For a replacement 
thermostat, contact the nearest Johnson Controls 
representative.      

Table 5:  Troubleshooting Details

Error/Trouble 
Condition

Possible Cause

Solution

Thermostat Cycles 
Online and Offline

Two or more controllers have the same address.

Change each duplicate address to a unique 
number.

There are Y or T taps on the N2 Bus, or the 
repeater has lost power or is wired incorrectly.

Refer to the 

N2 Communications Bus Technical 

Bulletin (LIT-636018)

.

Thermostat Does 
Not Come Online

Two or more controllers have the same address.

Change each duplicate address to a unique 
number.

The N2 Bus contains too many devices.

Do not exceed the maximum number of devices 
allowed on the N2 Bus per supervisory controller 
limitations.

The thermostat does not have power.

Apply power to the thermostat.

The N2 cable runs are broken.

Locate the break and correct the wiring.

The thermostat device type is incorrect.

Change the thermostat device type to VND.

N2 Bus is Offline

The wiring on the N2 Bus is broken.

Repair the wiring.

No point mapping has been entered.

Define the BAS dataset.

Table 6:  Display Messages

Display

Function

Frost ON

Indicates that heating is energized by the low limit frost protection room temperature setpoint.

Service

Indicates that there is a service alarm in accordance with the programmable Digital Inputs (DI1 or DI2).

Filter

Indicates that the filter(s) is dirty in accordance with the programmable Digital Inputs (DI1 or DI2).

Содержание TEC2104-3

Страница 1: ...injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or a...

Страница 2: ...he thermostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors incl...

Страница 3: ...ANT Make all wiring connections in accordance with local national and regional regulations Do not exceed the electrical ratings of the TEC2104 3 Thermostat Figure 5 Wiring the TEC2104 3 Thermostat 24...

Страница 4: ...etpoint if necessary to maintain the minimum deadband between the two setpoints The setpoints can be spread farther apart but can never be adjusted closer than 2F 1C apart If a supervisory controller...

Страница 5: ...m Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP1 ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP1 ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP ADI 10 N2 AI CSAD 100 F 37 5 C...

Страница 6: ...ithin the limits for a command results in an N2 Negative Acknowledge NAK error from the TEC2104 3 thermostat Overrides take precedence over any local adjustment or command in the TEC2104 3 thermostat...

Страница 7: ...o activate a setpoint adjustment Backlit Liquid Crystal Display LCD The TEC2104 3 Thermostat includes a 2 line 8 character backlit display Low level backlighting is present during normal operation and...

Страница 8: ...the YES key at the exit prompt To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for approximately 8 seconds...

Страница 9: ...cess No Access No Access Temporary Temperature Setpoints Access Access No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Pwr del1 Sets the delay time...

Страница 10: ...er a heating or cooling cycle has ended The fan delay is only active when the fan is in the Auto mode Com addr N2 network address at the thermostat coincides with the address assigned at the superviso...

Страница 11: ...n o n c Contact open Occupied contact closed Unoccupied n o Contact closed Occupied contact open Unoccupied The contact toggles with the internal Occupied Unoccupied schedule or the NSB contact on on...

Страница 12: ...er Resuming the Programmed Schedule This menu only appears when the thermostat is in the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts u...

Страница 13: ...Thermostat Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt appears on the disp...

Страница 14: ...ccupied and unoccupied states Smart Fan Mode smart Energizes the fan all the time for occupied states and only on a call for heating or cooling in unoccupied states This is the default setting To sele...

Страница 15: ...more controllers have the same address Change each duplicate address to a unique number The N2 Bus contains too many devices Do not exceed the maximum number of devices allowed on the N2 Bus per super...

Страница 16: ...acklit Display 40 0 F 40 0 C to 122 0 F 50 0 C in 0 5 Increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F...

Отзывы: