TEC2104-3 N2 Networked Multi-Stage Economizer Thermostat Installation Instructions
10
Heat cph
Sets the maximum number of
Heating cycles per hour.
Default:
4.0
Range:
3.0
to
8.0
cycles per hour
Cool cph
Sets the maximum number of
Cooling cycles per hour.
Default:
4.0
Range:
3.0
or
4.0
cycles per hour
Deadband
Sets the minimum deadband
between the heating and cooling
setpoints.
Default:
2.0F°/1.0C°
Range:
2.0F°/1.0C°
to
4.0F°/2.0C°
adjustable in 1.0F°/0.5C°
increments
Fan cont
Determines how the fan is activated
in response to a call for heating.
Fan cont
applies to W1 and W2 and
Fan Mode
auto
only.
Fan cont
does
not affect fan operation on a call for
cooling (Y1 and Y2).
Default:
on
(off):
The thermostat does not activate the fan in response to a call
for heating. The fan is activated by the equipment fan and limit
control.
(on):
Enables the thermostat to control the fan.
Fan del
Fan delay extends fan operation
after a heating or cooling cycle has
ended.
Default
off
(on):
Extends fan operation by 60 seconds after a heating or cooling
cycle has ended.
(off):
No extension of fan operation after a heating or cooling cycle
has ended.
The fan delay is only active when the fan is in the Auto mode.
Com addr
N2 network address at the
thermostat; coincides with the
address assigned at the supervisory
controller.
Default:
4
Range:
1
to
255
TOccTime
Sets the duration of the Temporary
Occupancy Time (when the
thermostat is in the Unoccupied
mode) when a Schedule Override
Function is enabled using either the
Main User Menu or DI1 or DI2
configured as a temporary override
remote contact (RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the up/down
arrow keys.
default:
3.0 hrs
Range:
0.0
to
12.0 hrs
adjustable in 1-hour increments
Cal RS
Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default:
0.0F°/0.0C°
Range:
-5.0F°/-2.5C°
to
5.0F°/2.5C°
adjustable in 1.0F°/0.5C°
increments
Cal OS
Sets the desired outdoor air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default:
0.0F°/0.0C°
Range:
-5.0F°/-2.5C°
to
5.0F°/2.5C°
adjustable in 1.0F°/0.5C°
increments
Table 2: Installer Configuration Menu (Part 3 of 5)
Parameter
Appearing
on Display
Description and Default
Selection Options