TEC2104-3 N2 Networked Multi-Stage Economizer Thermostat Installation Instructions

2

To install the thermostat:

1.

Use a Phillips-head screwdriver to remove the 
security screw on the bottom of the thermostat 
cover.

2.

Pull the bottom edge of the thermostat cover and 
open the thermostat as illustrated in Figure 1

3.

Carefully pull the locking tabs on the right side of 
the thermostat mounting base and unlock the 
Printed Circuit Board (PCB). Open the PCB to the 
left as illustrated in Figure 2. 

4.

Pull approximately 6 in. (152 mm) of wire from the 
wall and insert the wire through the hole in the 
thermostat mounting base.

5.

Align the thermostat mounting base on the wall and 
use the base as a template to mark the two 
mounting hole locations.

Note:

Be sure to position the thermostat mounting 

base so that the arrow on the base points upward to 
indicate the top of the thermostat.

6.

Drill a 3/16 in. (5 mm) hole at each of the two 
marked locations and tap nylon anchors (included 
with the thermostat) flush to the wall surface.

7.

Position the thermostat mounting base on the wall 
and use the two mounting screws (included with 
the thermostat) to secure the base to the surface 
as illustrated in Figure 3.

Note:

Be careful not to overtighten the mounting 

screws. 

8.

Swing the PCB back to the right and carefully snap 
it into the locking tabs on the thermostat mounting 
base.

9.

Pull the pull tabs on each of the connectors and 
remove the screw terminal blocks as illustrated in 
Figure 4. 

Figure 1: Removing the Thermostat Cover

F

IG

:c

v

r_

rm

v

l

Figure 2: Opening the Thermostat PCB

PCB
Locking
Tabs

F

IG

:p

rn

td

_

c

rc

t_

b

rd

Figure 3: Securing the Thermostat 

Mounting Base to the Wall

F

IG

:m

n

tn

g

_

b

s

Figure 4: Removing the Screw Terminal Blocks

F

IG

:t

rm

n

l_

b

lc

k

s

Содержание TEC2104-3

Страница 1: ...injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or a...

Страница 2: ...he thermostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors incl...

Страница 3: ...ANT Make all wiring connections in accordance with local national and regional regulations Do not exceed the electrical ratings of the TEC2104 3 Thermostat Figure 5 Wiring the TEC2104 3 Thermostat 24...

Страница 4: ...etpoint if necessary to maintain the minimum deadband between the two setpoints The setpoints can be spread farther apart but can never be adjusted closer than 2F 1C apart If a supervisory controller...

Страница 5: ...m Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP1 ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP1 ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP ADI 10 N2 AI CSAD 100 F 37 5 C...

Страница 6: ...ithin the limits for a command results in an N2 Negative Acknowledge NAK error from the TEC2104 3 thermostat Overrides take precedence over any local adjustment or command in the TEC2104 3 thermostat...

Страница 7: ...o activate a setpoint adjustment Backlit Liquid Crystal Display LCD The TEC2104 3 Thermostat includes a 2 line 8 character backlit display Low level backlighting is present during normal operation and...

Страница 8: ...the YES key at the exit prompt To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for approximately 8 seconds...

Страница 9: ...cess No Access No Access Temporary Temperature Setpoints Access Access No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Pwr del1 Sets the delay time...

Страница 10: ...er a heating or cooling cycle has ended The fan delay is only active when the fan is in the Auto mode Com addr N2 network address at the thermostat coincides with the address assigned at the superviso...

Страница 11: ...n o n c Contact open Occupied contact closed Unoccupied n o Contact closed Occupied contact open Unoccupied The contact toggles with the internal Occupied Unoccupied schedule or the NSB contact on on...

Страница 12: ...er Resuming the Programmed Schedule This menu only appears when the thermostat is in the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts u...

Страница 13: ...Thermostat Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt appears on the disp...

Страница 14: ...ccupied and unoccupied states Smart Fan Mode smart Energizes the fan all the time for occupied states and only on a call for heating or cooling in unoccupied states This is the default setting To sele...

Страница 15: ...more controllers have the same address Change each duplicate address to a unique number The N2 Bus contains too many devices Do not exceed the maximum number of devices allowed on the N2 Bus per super...

Страница 16: ...acklit Display 40 0 F 40 0 C to 122 0 F 50 0 C in 0 5 Increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F...

Отзывы: