TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller 
Installation Instructions

2

Canada  

Installation

Location Considerations

Locate a thermostat controller:

on a partitioning wall, approximately 1.5 m (5 ft) 
above the floor in a location of average 
temperature

away from direct sunlight, radiant heat, outside 
walls, outside doors, air discharge grills, or 
stairwells, or from behind doors

away from steam or water pipes, warm air stacks, 
unconditioned areas (not heated or cooled), or 
sources of electrical interference

For integrated Passive Infrared (PIR) models, make 
sure the thermostat controller is located centrally, 
where occupant movement is frequent.

Note:

Allow for vertical air circulation to the thermostat 

controller.

Wireless Signal Transmission Range

Line-of-sight transmission ranges between a 
TEC20 Coordinator and a TEC Wireless Thermostat 
Controller (or between TEC Wireless Thermostat 
Controllers) can be less than the recommended 
distances shown in Table 1. The effective transmission 
range for indoor applications varies because of Radio 
Frequency (RF) signal absorption and reflection due to 
metal obstructions, walls (or floors), and furniture found 
in typical building interiors.

 

For detailed information on locating devices for 
optimum signal strength, refer to the 

Wireless Metasys 

System Location Guide (LIT-12011294)

.

Installing the Thermostat Controller

Follow these steps to install the thermostat controller:

1.

Use a Phillips-head screwdriver to remove the 
security screw if it is installed on the bottom of the 
thermostat controller cover.

Note:

Normally, the security screw is packaged 

separately in a plastic bag with the thermostat 
controller. Skip this step if the screw is not installed 
on the bottom of the cover.

2.

Pull the bottom edge of the cover and open the 
thermostat controller as illustrated in Figure 1.

Note:

PIR Models have a wiring connection 

between the cover and the Printed Circuit Board 
(PCB). This connection allows for proper wiring of 
the occupancy sensor. Carefully remove the wiring 
connection from the PCB by pulling up on the 
connector block. 

Do not attempt to remove the 

connector block by pulling on the wires

.

This Class (A) digital apparatus meets all the 
requirements of the Canadian Interference-Causing 
Equipment Regulations.

Cet appareil numérique de la Classe (A) respecte 
toutes les exigences du Règlement sur le matériel 
brouilleur du Canada.

RF Transmitters: Industry Canada Statement

The term 

IC

 before the certification/registration 

number only signifies that the Industry Canada 
technical specifications were met.

Le terme « IC » précédant le numéro d'accréditation/
inscription signifie simplement que le produit est 
conforme aux spécifications techniques d'Industrie 
Canada.

Table 1:   Recommended Transmission Ranges

Type

Distance

Through Walls

 10 m (32.8 ft)

Open Space

 30 m (98.4 ft)

Figure 1: Removing the Thermostat Controller 

Cover (TEC2004-4+PIR Model Shown)

F

IG

:c

v

r_

rm

v

l

Содержание TEC2004-4

Страница 1: ...input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other pro...

Страница 2: ...Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controll...

Страница 3: ...rs and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount appl...

Страница 4: ...re checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment IMPORTANT Make all wiring connections in accordance with local national...

Страница 5: ...ooling The fan LED is on when the fan is on The heat LED is on when heating is on The cool LED is on when cooling is on The Status LED located beneath the cover flashes at 5 second intervals to provid...

Страница 6: ...figuration Menu to set up the thermostat controller for application specific operation To access the menu press and hold the MENU key for approximately 8 seconds Occupancy Sensor Operation TEC2004 4 P...

Страница 7: ...ded for approximately 8 seconds the thermostat controller reverts to the Status Display Menu Configuring the Wireless Mesh Network Settings Use the following process to configure the wireless mesh net...

Страница 8: ...11 to 26 Note Setting this parameter to 10 disables the function GET FROM Parameter not available at this time N A DI1 Configuration of Digital Input 1 Default None None No function is associated wit...

Страница 9: ...ked out if no airflow is detected 10 seconds after the fan Terminal G is energized Contact open no airflow contact closed airflow present MenuScro Gives the option of having the display continuously s...

Страница 10: ...equipment that already has its own anti short cycle timer Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of...

Страница 11: ...e in 0 5C 1 0F increments H stage Reverts the operation of a two stage thermostat controller to a single stage thermostat controller when the second heating stage is not needed Default 2 0 1 0 One Sta...

Страница 12: ...44 C mech Determines whether to allow mechanical cooling compressor operation if free cooling economizer operation cannot maintain the cooling setpoint Default off on Typically applies when the MS is...

Страница 13: ...de mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Resume Schedule prompt appears If the thermostat controller is in the override state this is the...

Страница 14: ...ate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu...

Страница 15: ...al Input Table 6 Accessories Order Separately Code Number Description SEN 600 1 Remote Indoor Air Temperature Sensor SEN 600 4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED TEC...

Страница 16: ...sed band Transmission Power 10 mW Maximum Temperature Range Backlit Display 40 0 C 40 0 F to 50 0 C 122 0 F Heating Control 4 5 C 40 0 F to 32 0 C 90 0 F in 0 5 Increments Cooling Control 12 0 C 54 0...

Отзывы: