TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller 
Installation Instructions

14

Entering Temporary Temperature Setpoints

To temporarily change the setpoint, press the 

UP/DOWN

 arrow keys to change the temporary 

setpoint for the current mode of operation.

Note:

Whether the thermostat controller is heating or 

cooling, the respective setpoint is temporarily adjusted. 
To toggle between the temporary heating and cooling 
setpoints, press the 

NO

 key while changing the 

temporary setpoints.

Ending Temporary Temperature Setpoints

The temporary setpoints remain in effect for the 
duration set in the 

TOccTime

 parameter or until 

manually released.

To release the temporary setpoint sooner, while in the 
Main User Menu:

1.

Press the 

YES

 key to the first prompt that appears.

2.

If the thermostat controller does not immediately 
return to the Status Display Menu, press the 

MENU

 

key again and press the 

YES

 key to exit the Main 

User Menu.

The setpoint reverts to the Permanent Temperature 
Setpoint.

Selecting the System Mode

The thermostat controller has four system modes:

Automatic Mode (auto):

 Automatic changeover 

between heating and cooling. This is the default 
setting.

Cooling Mode (cool):

 Cooling operation only

Heating Mode (heat):

 Heating operation only

Off Mode (off):

 The thermostat controller is off; 

however, when frost protection (

Frost pr

 

parameter) is enabled, the thermostat controller 
still calls for heat (if required).

To set the system mode while in the Main User Menu:

1.

Press the 

NO

 key to all prompts until the system 

mode prompt appears on the display. Press the 

YES

 key to select the desired system mode.

2.

Press the 

UP/DOWN

 arrow keys to locate the 

desired system mode. Press the 

YES

 key to select 

the desired system mode.

3.

Press the 

YES

 key to return to the Status Display 

Menu or press the 

NO

 key to return to the system 

mode selection menu.

Selecting the Fan Mode

The thermostat controller has three fan mode settings:

On Fan Mode (on):

 Energizes the fan all the time 

for both occupied and unoccupied states, even if 
the system mode is set to off.

Automatic Fan Mode (auto):

 Energizes the fan 

only on a call for heating or cooling, for both 
occupied and unoccupied states.

Smart Fan Mode (smart):

 Energizes the fan all 

the time for occupied states, and only on a call for 
heating or cooling in unoccupied states. This is the 
default setting.

To select the fan mode while in the Main User Menu:

1.

Press the 

NO

 key to all prompts until the fan mode 

prompt appears on the display. Press the 

YES

 key 

to set the fan mode.

2.

Press the 

UP/DOWN

 arrow keys to locate the 

desired fan mode. Press the 

YES

 key to select the 

desired fan mode.

3.

Press the 

YES

 key to return to the Status Display 

Menu or press the 

NO

 key to return to the fan 

mode selection menu.

Press the 

UP/DOWN

 arrow keys to 

set the temperature. Press the 

YES

 

key to store the value and advance to 
the next menu.

Press the 

YES

 key to change the 

unoccupied heating setpoint. Press 
the 

NO

 key to advance to the 

temperature display units.

Press the 

UP/DOWN

 arrow keys to 

set the temperature. Press the 

YES

 

key to store the value and advance to 
the next menu.

Press the 

YES

 key to set the display 

units to °F or °C. Press the 

NO

 key to 

advance to the temperature setpoint 
type menu.

Press the 

YES

 key to return to the 

Status Display Menu or press the 

NO

 

key to reenter the temperature 
setting menu.

Table 4:  Entering Permanent Temperature 

Setpoints (Part 2 of 2)

Thermostat 
Controller 
Display

Description

Unocc CL 
80.0

°

Unocc HT 
set? Y/N 

Unocc HT 
62.0

°

F

 

°

F/

°

set? Y/N 

Exit? 
 Y/N 

Содержание TEC2004-4

Страница 1: ...input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other pro...

Страница 2: ...Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controll...

Страница 3: ...rs and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount appl...

Страница 4: ...re checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment IMPORTANT Make all wiring connections in accordance with local national...

Страница 5: ...ooling The fan LED is on when the fan is on The heat LED is on when heating is on The cool LED is on when cooling is on The Status LED located beneath the cover flashes at 5 second intervals to provid...

Страница 6: ...figuration Menu to set up the thermostat controller for application specific operation To access the menu press and hold the MENU key for approximately 8 seconds Occupancy Sensor Operation TEC2004 4 P...

Страница 7: ...ded for approximately 8 seconds the thermostat controller reverts to the Status Display Menu Configuring the Wireless Mesh Network Settings Use the following process to configure the wireless mesh net...

Страница 8: ...11 to 26 Note Setting this parameter to 10 disables the function GET FROM Parameter not available at this time N A DI1 Configuration of Digital Input 1 Default None None No function is associated wit...

Страница 9: ...ked out if no airflow is detected 10 seconds after the fan Terminal G is energized Contact open no airflow contact closed airflow present MenuScro Gives the option of having the display continuously s...

Страница 10: ...equipment that already has its own anti short cycle timer Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of...

Страница 11: ...e in 0 5C 1 0F increments H stage Reverts the operation of a two stage thermostat controller to a single stage thermostat controller when the second heating stage is not needed Default 2 0 1 0 One Sta...

Страница 12: ...44 C mech Determines whether to allow mechanical cooling compressor operation if free cooling economizer operation cannot maintain the cooling setpoint Default off on Typically applies when the MS is...

Страница 13: ...de mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Resume Schedule prompt appears If the thermostat controller is in the override state this is the...

Страница 14: ...ate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu...

Страница 15: ...al Input Table 6 Accessories Order Separately Code Number Description SEN 600 1 Remote Indoor Air Temperature Sensor SEN 600 4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED TEC...

Страница 16: ...sed band Transmission Power 10 mW Maximum Temperature Range Backlit Display 40 0 C 40 0 F to 50 0 C 122 0 F Heating Control 4 5 C 40 0 F to 32 0 C 90 0 F in 0 5 Increments Cooling Control 12 0 C 54 0...

Отзывы: