TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller 
Installation Instructions

10

Cool min

2

Sets the Occupied and Unoccupied 
minimum Cooling setpoint values.
Default: 

12.0°C/54.0°F

Range: 

12.0°C/54.0°F

 to 

37.5°C/100.0°F

Pband

Proportional Band used by the PI 
temperature control loop of the 
thermostat controller.
Pband is not converted with C or F 
scale and is always shown with a 
range of 2 to 8.
Default: 

2

 (

2.0F°/1.1C°

)

Value

F Scale Pband/C Scale Pband

2

2.0F°/1.1C°

3

3.0F°/1.7C°

4

4.0F°/2.2C°

5

5.0F°/2.8C°

6

6.0F°/3.3C°

7

7.0F°/3.9C°

8

8.0F°/4.4C°

Note:

The use of a larger proportional band is not to use the 

thermostat controller as a discharge air controller device. The use of 
a larger proportional band can be used to solve issues for flawed 
HVAC design with basic sizing and thermostat controller location 
errors that cannot be worked around.

Anticycl

Anti-Short Cycle timer sets the 
minimum on/off times for heating 
and cooling stages.
Default: 

2.0 min

Range: 

0.0

 to 

5.0 min

 adjustable in 1-minute increments

Set the anti-short cycle timer to 

0.0 min

 for equipment that already 

has its own anti-short cycle timer.

Heat cph

Sets the maximum number of 
Heating cycles per hour.
Default: 

4.0

Range: 

3.0

 to 

8.0

 cycles per hour

Cool cph

Sets the maximum number of 
Cooling cycles per hour.
Default: 

4.0

Range: 

3.0

 or 

4.0

 cycles per hour

Deadband

Sets the minimum deadband 
between the heating and cooling 
setpoints.
Default: 

1.0C°/2.0F°

Range: 

1.0C°/2.0F°

 to 

2.0C°/4.0F°

 adjustable in 

0.5C°/1.0F°

 

increments

Fan cont

Determines how the fan is activated 
in response to a call for heating or 
cooling.
Default: 

on

(off):

 Enables the thermostat controller to activate the fan in 

response to a call for cooling only.

(on):

 Enables the thermostat controller to activate the fan in 

response to a call for heating or cooling.
When there is a call for auxiliary heating, the fan is activated by the 
equipment fan and limit control.

Fan del

Fan delay extends fan operation 
after a heating or cooling cycle has 
ended.
Default: 

off

(on):

 Extends fan operation by 60 seconds after a heating or cooling 

cycle has ended.

(off):

 No extension of fan operation after a heating or cooling cycle 

has ended.
The fan delay is only active when the fan is in the Auto mode.

Table 3:  Installer Configuration Menu  (Part 3 of 5)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание TEC2004-4

Страница 1: ...input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other pro...

Страница 2: ...Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controll...

Страница 3: ...rs and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount appl...

Страница 4: ...re checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment IMPORTANT Make all wiring connections in accordance with local national...

Страница 5: ...ooling The fan LED is on when the fan is on The heat LED is on when heating is on The cool LED is on when cooling is on The Status LED located beneath the cover flashes at 5 second intervals to provid...

Страница 6: ...figuration Menu to set up the thermostat controller for application specific operation To access the menu press and hold the MENU key for approximately 8 seconds Occupancy Sensor Operation TEC2004 4 P...

Страница 7: ...ded for approximately 8 seconds the thermostat controller reverts to the Status Display Menu Configuring the Wireless Mesh Network Settings Use the following process to configure the wireless mesh net...

Страница 8: ...11 to 26 Note Setting this parameter to 10 disables the function GET FROM Parameter not available at this time N A DI1 Configuration of Digital Input 1 Default None None No function is associated wit...

Страница 9: ...ked out if no airflow is detected 10 seconds after the fan Terminal G is energized Contact open no airflow contact closed airflow present MenuScro Gives the option of having the display continuously s...

Страница 10: ...equipment that already has its own anti short cycle timer Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of...

Страница 11: ...e in 0 5C 1 0F increments H stage Reverts the operation of a two stage thermostat controller to a single stage thermostat controller when the second heating stage is not needed Default 2 0 1 0 One Sta...

Страница 12: ...44 C mech Determines whether to allow mechanical cooling compressor operation if free cooling economizer operation cannot maintain the cooling setpoint Default off on Typically applies when the MS is...

Страница 13: ...de mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Resume Schedule prompt appears If the thermostat controller is in the override state this is the...

Страница 14: ...ate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu...

Страница 15: ...al Input Table 6 Accessories Order Separately Code Number Description SEN 600 1 Remote Indoor Air Temperature Sensor SEN 600 4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED TEC...

Страница 16: ...sed band Transmission Power 10 mW Maximum Temperature Range Backlit Display 40 0 C 40 0 F to 50 0 C 122 0 F Heating Control 4 5 C 40 0 F to 32 0 C 90 0 F in 0 5 Increments Cooling Control 12 0 C 54 0...

Отзывы: