TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller 
Installation Instructions

16

Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.

All other marks herein are the marks of their respective owners. © 2010 Johnson Controls, Inc.

Building Efficiency

507 E. Michigan Street, Milwaukee, WI  53202

Technical Specifications

TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controllers

Power Requirements

 

19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC Nominal, Class 2 or 
Safety Extra-Low Voltage (SELV)

Economizer Output Rating

0 to 10 VDC into 2k ohm Resistance (Minimum)

Relay/Triac Contact Rating

19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV

Digital Inputs

Voltage-Free Contacts across Terminal C to Terminals DI1 and DI2

Analog Inputs

Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative 
Temperature Coefficient (NTC) Thermistor Sensors

Wire Size

18 AWG Maximum, 22 AWG Recommended

Transmission Range

Through Walls: 

10 m (32.8 ft)

Line-of-Sight (Open Space): 

30 m (98.4 ft)

RF Band

Direct-Sequence Spread-Spectrum Transmission; 2.4 GHz unlicensed band

Transmission Power

10 mW  Maximum

Temperature Range

Backlit Display:

 -40.0°C/ -40.0°F to 50.0°C/122.0°F

Heating Control:

 4.5°C/40.0°F to 32.0°C/90.0°F in 0.5° Increments

Cooling Control: 

12.0°C/54.0°F to 100.0°F/38.0°C in 0.5° Increments

Temperature Sensor Type 

Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor

Resolution 

±0.1C°/±0.2F°

Control Accuracy

±0.5C°/±0.9F° at 21.0°C/70.0°F Typical Calibrated

Auxiliary/Outdoor Air 
Temperature Indication Range

-40.0°C/-40.0°F to 50.0°C/122.0°F

Minimum Deadband

1C°/2F° between Heating and Cooling

Ambient Conditions

Operating:

 0 to 50°C (32 to 122°F); 95% RH Maximum, Noncondensing

Storage:

-30 to 50°C (-22 to 122°F); 95% RH Maximum, Noncondensing

Compliance

United States:

UL Listed, File E27734, CCN XAPX, 
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to Part 15.247 Regulations for Low Power Unlicensed Transmitters

Canada:

UL Listed, File E27734, CCN XAPX7, 
Under CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003

Shipping Weight

TEC2004-4 Models:

 0.75 lb (0.34 kg)

TEC2004-4+PIR Models:

 0.77 lb (0.35 kg)

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these 
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or 
misuse of its products.

Содержание TEC2004-4

Страница 1: ...input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other pro...

Страница 2: ...Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controll...

Страница 3: ...rs and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount appl...

Страница 4: ...re checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment IMPORTANT Make all wiring connections in accordance with local national...

Страница 5: ...ooling The fan LED is on when the fan is on The heat LED is on when heating is on The cool LED is on when cooling is on The Status LED located beneath the cover flashes at 5 second intervals to provid...

Страница 6: ...figuration Menu to set up the thermostat controller for application specific operation To access the menu press and hold the MENU key for approximately 8 seconds Occupancy Sensor Operation TEC2004 4 P...

Страница 7: ...ded for approximately 8 seconds the thermostat controller reverts to the Status Display Menu Configuring the Wireless Mesh Network Settings Use the following process to configure the wireless mesh net...

Страница 8: ...11 to 26 Note Setting this parameter to 10 disables the function GET FROM Parameter not available at this time N A DI1 Configuration of Digital Input 1 Default None None No function is associated wit...

Страница 9: ...ked out if no airflow is detected 10 seconds after the fan Terminal G is energized Contact open no airflow contact closed airflow present MenuScro Gives the option of having the display continuously s...

Страница 10: ...equipment that already has its own anti short cycle timer Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of...

Страница 11: ...e in 0 5C 1 0F increments H stage Reverts the operation of a two stage thermostat controller to a single stage thermostat controller when the second heating stage is not needed Default 2 0 1 0 One Sta...

Страница 12: ...44 C mech Determines whether to allow mechanical cooling compressor operation if free cooling economizer operation cannot maintain the cooling setpoint Default off on Typically applies when the MS is...

Страница 13: ...de mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Resume Schedule prompt appears If the thermostat controller is in the override state this is the...

Страница 14: ...ate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu...

Страница 15: ...al Input Table 6 Accessories Order Separately Code Number Description SEN 600 1 Remote Indoor Air Temperature Sensor SEN 600 4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED TEC...

Страница 16: ...sed band Transmission Power 10 mW Maximum Temperature Range Backlit Display 40 0 C 40 0 F to 50 0 C 122 0 F Heating Control 4 5 C 40 0 F to 32 0 C 90 0 F in 0 5 Increments Cooling Control 12 0 C 54 0...

Отзывы: