TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller

Installation Instructions

13

Operation

Programming the Thermostat Controller

After configuring the thermostat controller by means of 
the Installer Configuration Menu, program its operating 
parameters by means of the Main User Menu. Access 
this menu by pressing the 

MENU

 key during normal 

operation. The Main User Menu contains the basic 
operating features of the thermostat controller.

The Main User Menu also uses Auto Help, which is 
displayed automatically in the menu when there is a 
pause in programming activity. To exit Auto Help, 
continue with the programming selection. When the 
thermostat controller is in the Main User Menu and is 
left unattended for 45 seconds, the menu reverts to the 
Status Display Menu.

Enabling Override Schedule

Note:

The Override Schedule prompt only appears 

when the thermostat controller is in the Unoccupied 
Mode. 

This menu selection gives the user the option of 
overriding the unoccupied setpoints with the occupied 
setpoints for the amount of time specified under the 

TOccTime

 parameter. See Table 3.

Note:

If one of the digital inputs is configured to 

operate as a remote override contact, this menu is 
disabled.

To override the unoccupied state while in the Main User 
Menu:

1.

Press the 

NO

 key to all prompts until the Override 

Schedule prompt appears. If the thermostat 
controller is in the unoccupied state, this is the first 
prompt.

2.

Press the 

YES

 key to enable the temporary 

override. The thermostat controller returns to the 
Status Display Menu.

When scrolling through the Status Display Menu, 
Override now appears for the schedule status 
parameter.

Resuming the Programmed Schedule

This menu only appears when the thermostat controller 
is in the override mode.

To resume the schedule while in the Main User Menu:

1.

Press the 

NO

 key to all prompts until the Resume 

Schedule prompt appears. If the thermostat 
controller is in the override state, this is the first 
prompt.

2.

Press the 

YES

 key to resume the programmed 

schedule.

The thermostat controller returns to the Status Display 
Menu.

Entering Permanent Temperature Setpoints

The first prompt appearing in the Main User Menu of 
the thermostat controller when in the occupied state is 
to set the permanent temperature setpoint. Permanent 
setpoints are stored in the programmed schedule.

To enter the permanent heating and cooling setpoints 
for the Occupied and Unoccupied Modes, follow the 
steps in Table 4. When changing the temperatures, 
press the keys once to change the temperature in 
0.5C°/0.5F° increments; press and hold down the keys 
to change the temperature in 5.0F°/5.0C° increments. 

Table 4:  Entering Permanent Temperature 

Setpoints (Part 1 of 2)

Thermostat 
Controller 
Display

Description

Press the 

MENU

 key while in the 

Status Display Menu to enter the 
Main User Menu.

Press the 

NO

 key to all prompts until 

the temperature setpoint prompt 
appears on the display (it may be the 
first prompt). Press the 

YES

 key to 

enter the temperature setting menu.

Press the 

YES

 key to change the 

occupied cooling setpoint. Press the 

NO

 key to advance to the occupied 

heating setpoint menu.

Press the 

UP/DOWN

 arrow keys to 

set the temperature. Press the 

YES

 

key to store the value and advance to 
the next menu.

Press the 

YES

 key to change the 

occupied heating setpoint. Press the 

NO

 key to advance to the unoccupied 

cooling setpoint menu.

Press the 

UP/DOWN

 arrow keys to 

set the temperature. Press the 

YES

 

key to store the value and advance to 
the next menu.

Press the 

YES

 key to change the 

unoccupied cooling setpoint. Press 
the 

NO

 key to advance to the 

unoccupied heating setpoint.

RoomTemp
75.0

°

Temperat
set? Y/N 

Cooling
set? Y/N 

Cooling
75.0

°

Heating
set? Y/N 

Heating
68.0

°

Unocc CL
set? Y/N

 

Содержание TEC2004-4

Страница 1: ...input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other pro...

Страница 2: ...Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controll...

Страница 3: ...rs and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount appl...

Страница 4: ...re checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment IMPORTANT Make all wiring connections in accordance with local national...

Страница 5: ...ooling The fan LED is on when the fan is on The heat LED is on when heating is on The cool LED is on when cooling is on The Status LED located beneath the cover flashes at 5 second intervals to provid...

Страница 6: ...figuration Menu to set up the thermostat controller for application specific operation To access the menu press and hold the MENU key for approximately 8 seconds Occupancy Sensor Operation TEC2004 4 P...

Страница 7: ...ded for approximately 8 seconds the thermostat controller reverts to the Status Display Menu Configuring the Wireless Mesh Network Settings Use the following process to configure the wireless mesh net...

Страница 8: ...11 to 26 Note Setting this parameter to 10 disables the function GET FROM Parameter not available at this time N A DI1 Configuration of Digital Input 1 Default None None No function is associated wit...

Страница 9: ...ked out if no airflow is detected 10 seconds after the fan Terminal G is energized Contact open no airflow contact closed airflow present MenuScro Gives the option of having the display continuously s...

Страница 10: ...equipment that already has its own anti short cycle timer Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of...

Страница 11: ...e in 0 5C 1 0F increments H stage Reverts the operation of a two stage thermostat controller to a single stage thermostat controller when the second heating stage is not needed Default 2 0 1 0 One Sta...

Страница 12: ...44 C mech Determines whether to allow mechanical cooling compressor operation if free cooling economizer operation cannot maintain the cooling setpoint Default off on Typically applies when the MS is...

Страница 13: ...de mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Resume Schedule prompt appears If the thermostat controller is in the override state this is the...

Страница 14: ...ate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu...

Страница 15: ...al Input Table 6 Accessories Order Separately Code Number Description SEN 600 1 Remote Indoor Air Temperature Sensor SEN 600 4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED TEC...

Страница 16: ...sed band Transmission Power 10 mW Maximum Temperature Range Backlit Display 40 0 C 40 0 F to 50 0 C 122 0 F Heating Control 4 5 C 40 0 F to 32 0 C 90 0 F in 0 5 Increments Cooling Control 12 0 C 54 0...

Отзывы: