TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller 
Installation Instructions

12

Aux cont

Energizes peripheral devices 
(lighting equipment, exhaust fans, 
and economizers).
Default: 

n.o.

Note:

The contact toggles with the 

internal Occupied/Unoccupied 
schedule (or the NSB contact on 
one of the digital inputs, if used).

(n.c.):

 Contact open = Occupied; contact closed = Unoccupied

(n.o.):

 Contact closed = Occupied; contact open = Unoccupied

Chngstpt

2

Sets the economizer changeover 
strategy, based on the outdoor air 
temperature. Requires that an 
outdoor air temperature sensor be 
installed and connected.
When the OA temperature is below 
the changeover setpoint, free 
cooling is used (economizer 
operation). When the OA 
temperature is above the setpoint, 
mechanical cooling is used 
(compressor operation).
Default: 

13.0°C/55.0°F

Range: 

-10.0°C/14.0°F

 to 

21.0°C/70.0°F

Min pos

Sets the minimum position for the 
OA dampers on the economizer. 
These dampers are energized to 
minimum position when the fan 
(Terminal G) is energized and the 
thermostat controller is in the 
Occupied mode. When the 
schedule is in the Unoccupied 
mode, the minimum position is 0%.
Default: 

0.0%

Range: 

0.0

 to 

100.0%

 equals 0 to 10 VDC output range

% OA

Setting for 0 to 10 VDC 

Actuator

Setting for 2 to 10 VDC 

Actuator

(0.0%)

0%

0 to 20%

(5.0%)

5%

24%

(10.0%)

10%

28%

(15.0%)

15%

32%

(20.0%)

20%

36

%

(25.0%)

25%

40%

(30.0%)

30%

44%

C mech

Determines whether to allow 
mechanical cooling (compressor 
operation) if free cooling 
(economizer operation) cannot 
maintain the cooling setpoint.
Default: 

off

(on):

 Typically applies when the MS is installed before the 

mechanical cooling refrigeration coils in the mixing plenum. In this 
scenario, mechanical cooling is allowed when free cooling cannot 
maintain the cooling setpoint.

(off):

 Typically applies when the remote Mixed air Sensor (MS) is 

installed after the mechanical cooling refrigeration coils. In this 
scenario, mechanical cooling will never operate at the same time as 
free cooling.

Mix stpt

2

Establishes the mixed air 
temperature when operating in the 
economizer mode.
Default: 

55.0°F/13.0°C

Range: 

50.0°F/10.0°C

 to 

90.0°/32.0°C

MS temp

Displays the mixed air temperature. 
Requires that an MS be installed 
and connected.
Default: 

N/A

The mixed air temperature can be used to help service and 
troubleshoot the equipment and the economizer operation. The 
mixed air temperature is only accessible via the Installer 
Configuration Menu.

1.

When adjusting the numeric value, press the 

UP

 or 

DOWN

 arrow key to change the value by single increments; press and 

hold the 

UP

 or 

DOWN

 arrow key to change the numeric value in increments of ten.

2.

When adjusting the temperature, press the 

UP

 or 

DOWN

 arrow key to change the value in 0.5F°/0.5C° increments; press 

and hold the 

UP

 or 

DOWN

 arrow key to change the value in 5.0F°/5.0C° increments.

Table 3:  Installer Configuration Menu  (Part 5 of 5)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание TEC2004-4

Страница 1: ...input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other pro...

Страница 2: ...Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controll...

Страница 3: ...rs and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount appl...

Страница 4: ...re checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment IMPORTANT Make all wiring connections in accordance with local national...

Страница 5: ...ooling The fan LED is on when the fan is on The heat LED is on when heating is on The cool LED is on when cooling is on The Status LED located beneath the cover flashes at 5 second intervals to provid...

Страница 6: ...figuration Menu to set up the thermostat controller for application specific operation To access the menu press and hold the MENU key for approximately 8 seconds Occupancy Sensor Operation TEC2004 4 P...

Страница 7: ...ded for approximately 8 seconds the thermostat controller reverts to the Status Display Menu Configuring the Wireless Mesh Network Settings Use the following process to configure the wireless mesh net...

Страница 8: ...11 to 26 Note Setting this parameter to 10 disables the function GET FROM Parameter not available at this time N A DI1 Configuration of Digital Input 1 Default None None No function is associated wit...

Страница 9: ...ked out if no airflow is detected 10 seconds after the fan Terminal G is energized Contact open no airflow contact closed airflow present MenuScro Gives the option of having the display continuously s...

Страница 10: ...equipment that already has its own anti short cycle timer Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of...

Страница 11: ...e in 0 5C 1 0F increments H stage Reverts the operation of a two stage thermostat controller to a single stage thermostat controller when the second heating stage is not needed Default 2 0 1 0 One Sta...

Страница 12: ...44 C mech Determines whether to allow mechanical cooling compressor operation if free cooling economizer operation cannot maintain the cooling setpoint Default off on Typically applies when the MS is...

Страница 13: ...de mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Resume Schedule prompt appears If the thermostat controller is in the override state this is the...

Страница 14: ...ate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu...

Страница 15: ...al Input Table 6 Accessories Order Separately Code Number Description SEN 600 1 Remote Indoor Air Temperature Sensor SEN 600 4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED TEC...

Страница 16: ...sed band Transmission Power 10 mW Maximum Temperature Range Backlit Display 40 0 C 40 0 F to 50 0 C 122 0 F Heating Control 4 5 C 40 0 F to 32 0 C 90 0 F in 0 5 Increments Cooling Control 12 0 C 54 0...

Отзывы: