TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
Installation Instructions
7
Configuring the Thermostat Controller
The thermostat controller ships from the factory with
default settings for all configurable parameters. The
default settings are shown in Table 3. To reconfigure
the parameters via the thermostat controller, follow the
steps in this section.
1.
To access the Installer Configuration Menu, press
and hold the
MENU
key for approximately
8 seconds.
Note:
If the
Password
parameter is configured,
Password 0 appears on the thermostat controller
display indicating that the configured password is
required to proceed. Use the
UP/DOWN
arrow
keys to indicate the configured password, then
press the
MENU
key to proceed through the
Installer Configuration Menu parameters.
2.
Once the Installer Configuration Menu begins,
release and press the
NO
key to scroll through the
parameters listed in Table 3.
3.
When the desired parameter is displayed, use the
YES
key to choose the desired selection option.
4.
Press the
YES
key and then the
NO
key to
continue scrolling through the parameters.
When the thermostat controller is in the Installer
Configuration Menu and left unattended for
approximately 8 seconds, the thermostat controller
reverts to the Status Display Menu.
Configuring the Wireless Mesh Network
Settings
Use the following process to configure the wireless
mesh network settings.
1.
Select a
PAN ID
and
Channel
. Use these same
values for every TEC Wireless Thermostat
Controller (and the associated coordinator) on the
same wireless mesh network.
2.
Select a
Com Address
for each TEC Wireless
Thermostat Controller (1 to 254). This address
must be unique to each thermostat controller on
the same wireless network (that is, unique to the
PAN ID
and
Channel
combination).
After configuring the wireless mesh network settings,
refer to the
TEC20xx-4 and TEC20xx-4+PIR Series
Wireless Thermostat Controller System Technical
Bulletin (LIT-12011596)
for directions on integrating the
TEC20xx-4 and TEC20xx-4+PIR Series Wireless
Thermostat Controllers and TEC20 Coordinator with a
supervisory controller.
Configuring Inputs DI1 and DI2
When DI1 and DI2 are configured for an alarm
condition, an alarm condition is displayed locally when
the input is closed. An alarm message is included on
the scrolling Status Display Menu and when the
message is displayed, the backlight momentarily
lights up.
Both inputs can be configured to the Selection Options
included in Table 3.
Figure 7: Increasing Room Temperature Setpoints
Occ Heat
= 72°F
Occ Cool
= 75°F
Unocc Heat
= 65°F
Room Temperature
FI
G
:r
m
_t
m
p