background image

TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller

Installation Instructions

7

 

Configuring the Thermostat Controller

The thermostat controller ships from the factory with 
default settings for all configurable parameters. The 
default settings are shown in Table 3. To reconfigure 
the parameters via the thermostat controller, follow the 
steps in this section.

1.

To access the Installer Configuration Menu, press 
and hold the 

MENU

 key for approximately 

8 seconds. 

Note:

If the 

Password

 parameter is configured, 

Password 0 appears on the thermostat controller 
display indicating that the configured password is 
required to proceed. Use the 

UP/DOWN

 arrow 

keys to indicate the configured password, then 
press the 

MENU

 key to proceed through the 

Installer Configuration Menu parameters.

2.

Once the Installer Configuration Menu begins, 
release and press the 

NO

 key to scroll through the 

parameters listed in Table 3. 

3.

When the desired parameter is displayed, use the 

YES

 key to choose the desired selection option. 

4.

Press the 

YES

 key and then the 

NO

 key to 

continue scrolling through the parameters.

When the thermostat controller is in the Installer 
Configuration Menu and left unattended for 
approximately 8 seconds, the thermostat controller 
reverts to the Status Display Menu.

Configuring the Wireless Mesh Network 
Settings

Use the following process to configure the wireless 
mesh network settings.

1.

Select a 

PAN ID

 and 

Channel

. Use these same 

values for every TEC Wireless Thermostat 
Controller (and the associated coordinator) on the 
same wireless mesh network.

2.

Select a 

Com Address

 for each TEC Wireless 

Thermostat Controller (1 to 254). This address 
must be unique to each thermostat controller on 
the same wireless network (that is, unique to the 

PAN ID

 and 

Channel

 combination).

After configuring the wireless mesh network settings, 
refer to the 

TEC20xx-4 and TEC20xx-4+PIR Series 

Wireless Thermostat Controller System Technical 
Bulletin (LIT-12011596)

 for directions on integrating the 

TEC20xx-4 and TEC20xx-4+PIR Series Wireless 
Thermostat Controllers and TEC20 Coordinator with a 
supervisory controller.

Configuring Inputs DI1 and DI2

When DI1 and DI2 are configured for an alarm 
condition, an alarm condition is displayed locally when 
the input is closed. An alarm message is included on 
the scrolling Status Display Menu and when the 
message is displayed, the backlight momentarily 
lights up.

Both inputs can be configured to the Selection Options 
included in Table 3. 

Figure 7: Increasing Room Temperature Setpoints

Occ Heat

= 72°F

Occ Cool

= 75°F

Unocc Heat

= 65°F

Room Temperature

FI

G

:r

m

_t

m

p

Содержание TEC2004-4

Страница 1: ...input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other pro...

Страница 2: ...Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controll...

Страница 3: ...rs and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount appl...

Страница 4: ...re checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment IMPORTANT Make all wiring connections in accordance with local national...

Страница 5: ...ooling The fan LED is on when the fan is on The heat LED is on when heating is on The cool LED is on when cooling is on The Status LED located beneath the cover flashes at 5 second intervals to provid...

Страница 6: ...figuration Menu to set up the thermostat controller for application specific operation To access the menu press and hold the MENU key for approximately 8 seconds Occupancy Sensor Operation TEC2004 4 P...

Страница 7: ...ded for approximately 8 seconds the thermostat controller reverts to the Status Display Menu Configuring the Wireless Mesh Network Settings Use the following process to configure the wireless mesh net...

Страница 8: ...11 to 26 Note Setting this parameter to 10 disables the function GET FROM Parameter not available at this time N A DI1 Configuration of Digital Input 1 Default None None No function is associated wit...

Страница 9: ...ked out if no airflow is detected 10 seconds after the fan Terminal G is energized Contact open no airflow contact closed airflow present MenuScro Gives the option of having the display continuously s...

Страница 10: ...equipment that already has its own anti short cycle timer Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of...

Страница 11: ...e in 0 5C 1 0F increments H stage Reverts the operation of a two stage thermostat controller to a single stage thermostat controller when the second heating stage is not needed Default 2 0 1 0 One Sta...

Страница 12: ...44 C mech Determines whether to allow mechanical cooling compressor operation if free cooling economizer operation cannot maintain the cooling setpoint Default off on Typically applies when the MS is...

Страница 13: ...de mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Resume Schedule prompt appears If the thermostat controller is in the override state this is the...

Страница 14: ...ate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu...

Страница 15: ...al Input Table 6 Accessories Order Separately Code Number Description SEN 600 1 Remote Indoor Air Temperature Sensor SEN 600 4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED TEC...

Страница 16: ...sed band Transmission Power 10 mW Maximum Temperature Range Backlit Display 40 0 C 40 0 F to 50 0 C 122 0 F Heating Control 4 5 C 40 0 F to 32 0 C 90 0 F in 0 5 Increments Cooling Control 12 0 C 54 0...

Отзывы: