Johnson Controls TEC2004-4 Скачать руководство пользователя страница 11

TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller

Installation Instructions

11

TOccTime

Sets the duration of the Temporary 
Occupancy Time (when the 
thermostat controller is in the 
Unoccupied mode) when a 
Schedule Override Function is 
enabled using either the Main User 
Menu or DI1 or DI2 configured as a 
temporary override remote contact 
(RemOVR).
Sets the effective duration of the 
Temporary heating or cooling 
setpoints set using the 

UP/DOWN

arrow keys.

Default: 

3.0 hrs

Range: 

0.0

 to 

12.0 hrs

 adjustable in 1-hour increments

Cal RS

Sets the desired room air 
temperature sensor calibration 
(offset). The offset can be added to 
or subtracted from the actual 
displayed room temperature.
Default: 

0.0C°/0.0C°F

Range:

 

-2.5C°/-5.0F°

 to 

2.5C°/5.0F°

 adjustable in 0.5C°/1.0F° 

increments

Cal OS

Sets the desired outdoor air 
temperature sensor calibration 
(offset). The offset can be added to 
or subtracted from the actual 
displayed room temperature.
Default: 

0.0C°/0.0F°

Range: 

-2.5C°/-5.0F°

 to 

2.5C°/5.0F°

 adjustable in 0.5C°/1.0F° 

increments

H stage

Reverts the operation of a two-stage 
thermostat controller to a 
single-stage thermostat controller 
when the second heating stage is 
not needed.
Default: 

2.0

(1.0): 

One Stage

(2.0): 

Two Stages

C stage

Reverts the operation of a two-stage 
thermostat controller to a 
single-stage thermostat controller 
when the second cooling stage is 
not needed.
Default: 

2.0

(1.0):

 One Stage

(2.0):

 Two Stages

H lock

Disables heating stage(s) operation 
when the outside air temperature is 
greater than the configured value. If 
the fan mode is set to Auto or 
Smart, the fan output is also 
disabled. Requires that an outside 
air temperature sensor be installed 
and connected.
Default: 

120°F/49°C

Range: 

-15°F/-26°C

 to 

120°F/49°C

 adjustable in 5F°/5C° 

increments

C lock

Disables cooling stage(s) operation 
when the outside air temperature is 
less than the configured value. If the 
fan mode is set to Auto or Smart, 
the fan output is also disabled. 
Requires that an outside air 
temperature sensor be installed and 
connected.
Default: 

-40°F/-40°C

Range: 

-40°F/-40°C

 to 

95°F/35°C

 adjustable in 5F°/5C° increments

Table 3:  Installer Configuration Menu  (Part 4 of 5)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание TEC2004-4

Страница 1: ...input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other pro...

Страница 2: ...Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controll...

Страница 3: ...rs and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount appl...

Страница 4: ...re checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment IMPORTANT Make all wiring connections in accordance with local national...

Страница 5: ...ooling The fan LED is on when the fan is on The heat LED is on when heating is on The cool LED is on when cooling is on The Status LED located beneath the cover flashes at 5 second intervals to provid...

Страница 6: ...figuration Menu to set up the thermostat controller for application specific operation To access the menu press and hold the MENU key for approximately 8 seconds Occupancy Sensor Operation TEC2004 4 P...

Страница 7: ...ded for approximately 8 seconds the thermostat controller reverts to the Status Display Menu Configuring the Wireless Mesh Network Settings Use the following process to configure the wireless mesh net...

Страница 8: ...11 to 26 Note Setting this parameter to 10 disables the function GET FROM Parameter not available at this time N A DI1 Configuration of Digital Input 1 Default None None No function is associated wit...

Страница 9: ...ked out if no airflow is detected 10 seconds after the fan Terminal G is energized Contact open no airflow contact closed airflow present MenuScro Gives the option of having the display continuously s...

Страница 10: ...equipment that already has its own anti short cycle timer Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of...

Страница 11: ...e in 0 5C 1 0F increments H stage Reverts the operation of a two stage thermostat controller to a single stage thermostat controller when the second heating stage is not needed Default 2 0 1 0 One Sta...

Страница 12: ...44 C mech Determines whether to allow mechanical cooling compressor operation if free cooling economizer operation cannot maintain the cooling setpoint Default off on Typically applies when the MS is...

Страница 13: ...de mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Resume Schedule prompt appears If the thermostat controller is in the override state this is the...

Страница 14: ...ate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu...

Страница 15: ...al Input Table 6 Accessories Order Separately Code Number Description SEN 600 1 Remote Indoor Air Temperature Sensor SEN 600 4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED TEC...

Страница 16: ...sed band Transmission Power 10 mW Maximum Temperature Range Backlit Display 40 0 C 40 0 F to 50 0 C 122 0 F Heating Control 4 5 C 40 0 F to 32 0 C 90 0 F in 0 5 Increments Cooling Control 12 0 C 54 0...

Отзывы: