HELTUN HEATING THERMOSTAT

HE-ZW-THERM-FL2   USER MANUAL  V1.0

OVERVIEW 

This is a programmable electronic room heating thermostat for flush mounting into most 
standard wall boxes. It is designed to maintain a constant ambient temperature, the criteria of 
which can be simultaneously either floor, room or both temperature sensors. 
It is recommended for the control of electric heating devices (radiators, convectors, electric 
fireplace), boilers or electric under floor heating. The heating element is directly controlled by 
a single pole switch. The maximum loading for the thermostat is 16A over which a contactor 
will be required. (16A – 3600W @ 220V/240V.)

The thermostat has an LCD screen, six sensitive capacitive touch control buttons and two 
temperature sensors (external NTC floor sensor and a built-in room air temperature sensor). 
The thermostat is also equipped with built-in humidity, illumination and energy consumption 
sensors. 

The thermostat has an integrated 5th generation secure Z-Wave module which allows to use 
the  device  with  Z-Wave  Home  Automation  systems  such  as  Fibaro,  Vera,  Zipato, 
SmartThings, Z-Way, HomeSeer and others. The thermostat can be associated and control 
up to 10 Z-Wave devices (relays, switchers etc.)

One of six operation modes can be selected either manually or via the Z-Wave controller / 
gateway. The 6 operating modes are: COM - most comfortable (full power) mode, TIME – 
control the temperature by day time, DRY - floor quick drying mode, ECO – energy saving 
mode, VAC – vacation mode and MAN - manual control mode. The thermostat protects the 
floor from overheating by automatically switching off the load when the temperature reaches 
a maximum of 40°C.

The LCD screen with white icons has a user-friendly interface, displaying:
floor temperature, air temperature, humidity level, user set temperature, operating mode, 
time, weekday, relay and Z-Wave network statuses.

TECHNICAL SPECIFICATIONS

Front frame dimensions: 89х89х9mm
Back dimensions: 53х53х28mm 
Material: Flame retardant plastic, tempered glass
4 frame colors: Silver, Chrome, Black, White
6 glass colors: White, Black, Yellow, Green, Red, Blue
LCD: 73x42mm, black with white icons
6 sensitive capacitive touch buttons
Operating temperature: 0°С – +50°С
Power supply: 100V – 230VAC, 50Hz/60Hz
Power consumption: 1.5W
Maximum resistive load: 16А, 3600W @220V
Relay life time: 100.000 switches
Internal ambient brightness sensor
Internal temperature sensor

Measurement range: -30°C to +80°C
Accuracy: ±0.5°C 

Internal humidity sensor

Measurement range: 0 – 80%RH
Accuracy: ±3.0%RH 

External floor temperature sensor

NTC 10kOhm
Measurement range: -30°C to +80°C
Accuracy: ±0.5°C 

Energy consumption meter
IP class: IP21
Z-Wave Plus SDK: V6.71

FUNCTIONAL SPECIFICATIONS

Inclusion/exclusion into/from z-wave network

Non Secure
S0 secure
S2 unauthorized, S2 authorized

Association control of 10 devices from network
6 operation modes with individual temperature set point: 

COM, ECO, VAC, DRY, TIME, MANUAL

4 time schedule for 7 days of the week:

Morning, Day, Evening, Night

Choosing a temperature sensor for operation:

Floor temperature only
Air temperature only
Floor + Air temperature
Power regulator (Automatic ON/OFF timer)

Usable with different NTC-sensor (1kOhm - 100kOhm)
Temperature sensors calibration
Temperature set intervals: 4.0°C to 37.0°C
Temperature limiter: 40.0°C
Choosing a temperature hysteresis: 0.1°C - 9.5°C
Choosing a degree (Celsius / Fahrenheit)
Adjustable LCD brightness: Auto or Manual
LCD standby mode
Child lock (touch buttons lock)
Consumption meter
Factory reset
OTA function (Firmware update over the air).

INSTALLATION

 

We recommend the installation conforms to your local regulations and is undertaken by a 
qualified electrical engineer. Positioning of the thermostat is of the utmost importance and 
must be away from sunlight and sources of direct heat. We recommend installation about 1.5 
metres above the floor. 

Electrical power must be switched off during all aspects of installation. 

1. Remove the front cover and back plate of the thermostat from the main box. 
2. ENSURING THE POWER IS OFF and using a small cross head (Phillips) screwdriver 
connect the wires to the thermostat terminals: 
IN: Power connection 
HEATING: Heating element connection
3. If using the thermostat for floor heating, connect the NTC temperature sensor wires to 
terminals NTC. 10 kΩ NTC sensor is included in the box but any NTC sensor can be used. If 
another sensor other than 10 kΩ NTC is used then ensure changing the sensor value in the 
thermostat settings (Parameter 17 - FSr).
4. If using an external device for the thermostat modes control, connect its dry contacts to 
terminals EXT.
5. Making sure “TOP” is uppermost secure the back plate into the wall mounting box using 
the  screws  provided.  Install  the  thermostat  body  by  carefully  aligning  the  top  snap 
connectors and then pushing on the front cover with gentle pressure ensuring it snaps firmly 
into position all the way round. 
6. Switch On the main power and the thermostat will start up showing the original default 
factory settings. 
7. Remove protective film by pulling the tab in the top right hand side.

DISASSEMBLY

1. ENSURE POWER IS SWITCHED OFF AND SCREEN IS BLANK.
2. To remove thermostat body grasp firmly and pull back from the bottom until all tabs 
disconnect.
3. Remove screws from back plate and disconnect the wires.

TOUCH PANEL OPERATION 

The touch panel has six touch buttons which require minimal pressure to operate.

Plus 
Minus
Time
Settings
Manual Heating
Mode

“   “ key will increase set point temperature by 0.5°C (or 1°F), and “   “ key will decrease set 
point temperature by 0.5°C (or 1°F). The set point temperature is displayed in the bottom left 
corner of the display as “SET TEMP”.

Note:

 The minimum set point is 4.0°C (39°F) and the maximum set point is 37.0°C (99°F).

The  thermostat  has  two  working  modes:  HEATING  and  IDLE.  In  HEATING  mode  the 
operating state icon       will appear on the right bottom corner of the display, and the icon will 
disappear in the  IDLE mode.

OPERATION MODE

 

Current mode is displayed in the middle right line of display under “HEATING MODE” field.
The thermostat has 6 operating modes: 
COM – general comfort (full power) mode. 
TIME – time mode allows to set a different temperature for different periods of the day 
DRY – fast floor drying.
ECO – economy (power efficient / energy saving) mode.
VAC – vacation (away) mode 
MAN – manual mode.

Change the mode by touching the MODE key and reselecting as above. 
Each operating modes has an individual temperature set points. The thermostat will operate 
automatically depending on the current SET TEMP point. To change the set point values 
choose the desired mode and press “

+

” key to increase or press “

” key to reduce the value. 

Alternatively control from your Z-wave gateway.

MAN MODE 
In this mode the thermostat logic is disabled and the heating state can be switched On/Off 
manually by pressing the         key.
Note: if the MAN mode is enabled the SET POINT will indicate OFF.

COM (comfort) MODE
This mode is recommended for normal comfort.
Factory default set point is 25.0°C (77°F)

DRY MODE
This mode is recommended for use if a high floor temperature is required for a limited period 
of time for example after floor washing. By choosing DRY mode the thermostat will increase 
the  temperature  to  the  selected  set  point  for  a  limited  time  specified  in  the  “Dry  Time” 
parameter.  The  time  range  of  5-90  minutes  can  be  selected.  After  the  drying  time  the 
thermostat will automatically change back to  the TIME mode.
To change the Dry Time, go to “Settings Mode” by pressing the      key for 3 seconds. Use the 
keys        or          to scroll the menu to Parameter 07, then use keys “

+

” and “

” to increase or 

reduce the time. The value of Dry Time is in minutes.
Factory default Dry time is 30 min.
Factory default set point is 30.0°C (86°F)

ECO (energy saving) MODE 
This mode can be used if lower temperature and energy consumption is required. It can also 
be used at night or when absent from all or part of the property for a length of time.
Factory default set point is 20.0°C (68°F)

VAC (vacation) MODE
This mode is recommended for use when absent.
Factory default set point is 15.0°C (59°F)

Note:

 The minimum set point for each mode is 4.0°C (39°F) and the maximum set point is 

37.0°C (99°F).

TIME MODE

Adjust home temperature according to personal habits by reducing it whilst away from home 
and increasing in the evenings and early mornings. 

The thermostat can be set individually for morning, day, evening and night. For example, it 
can be assigned for Morning period start at 7.00, then Day starting at 9.00 (when absent for 
work etc.), then Evening starting at 18:00 (half an hour before occupants return). The Night 
regime then begins at 23.30 (bedtime). 

Separate temperature settings can be made for all 4 periods for every day of the week.

To set up the time and temperature for each period go to the Time menu by pressing and 
holding the      key for 3 seconds. The display will show the Time menu.

To set up the start time for each period choose the period by pressing the      key than adjust 
the time by pressing the        key for increase or MODE key for decrease. Do this action for all 
4 periods: Morning, Day, Evening & Night.

To set up the temperature choose the week day by pressing the      key, choose the period by 
pressing         key and adjust the temperature by pressing “+” or “–“ keys. Do this action for 
every day of the week.

Note:

  TIME  mode  works  only  in  case  of  the  correct  time  being  set.  The  time  can  be 

automatically corrected by polling from your gateway if the Parameter 8 value is 1 or set 
manually in Parameters 10, 11 and 12 in the settings menu.

Note:

 In the TIME mode the SET POINT of the thermostat will be automatically changed 

depending on the period. The SET POINT can be  adjusted manually out of the TIME menu 
but it will be effective only until  the next period.

SETTINGS MODE

To activate the settings mode, press and hold the      key for 3 seconds. The display will show 
the settings menu. In the top left corner is the parameter number, in the left bottom corner is 
the parameter display indication (the parameter name) and in the right top corner is the 
parameter value. 

To scroll the menu navigation just press the        key to go up and the MODE key to go down. 
To change the parameters value press the “+” or “-” keys.

Param

number

Param
value

Param 
number
increase

Param 
number
reduce

Param 

Value

Reduce

Param 

Value

Increase

Param

name

 

To leave the Settings mode to go to the main display mode press and hold the     key for 3 
seconds.

The thermostat will automatically leave to the display mode if no action is detected for 10 
seconds.

PARAMETERS LIST

Parameter 01 (dEg) – Degree mode

Celsius (°C) or Fahrenheit (°F) degree mode can be choosen. Floor and air temperature, as 
well as set point and all parameters will be indicated in the chosen mode.
Factory default value is Celsius (°C).

Parameter 02 (In1) – External input mode

The thermostat can be connected to an external device (like security system) dry output 
contacts and control the thermostat operating modes depending on the contacts state.
If parameter value is 0 no action will be take (the input state is ignored by the thermostat 
logic). If parameter value is 1 the thermostat will be switched to the operating mode selected 
in Parameter 3 if the output was short-circuited. The thermostat will go back to previous mode 
as soon as the input is open.

 I

f parameter value is 2 the thermostat will be switched to the 

operating mode selected in Parameter 3 if the output was short-circuited. But the thermostat 
will not undertake any action if the input is open again.
Factory default value is 1.

Parameter 03 (In2) – Operating mode for external input action

This parameter allows selecting which operating mode the thermostat should go to if the 
external input is short-circuited. 1=COM, 2=TIME, 3=DRY, 4=ECO, 5=VAC, 6=MAN.

Note: 

When thermostat goes to MAN mode it will be in IDLE state till HEATING key is not 

pressed manually. 
Factory default value is 2

Parameter 04 (SEn) – Source sensor

The thermostat has seven regulation modes based on different sensors values. Use keys “+” 
and “-” to choose follow modes:
1) A  –  Air sensor 
2) AF  –  Air  Floor sensor 
3) F  –  Floor sensor
4) FA  –  Floor  Air sensor
5) P  –  Power regulator 
6) PA  –  Power reg Air sensor 
7) PF  –  Power reg Floor sensor

1) A – Air sensor: Regulation (heating control) is based on the SET POINT applied to the 
internal room air temperature sensor. 
2) AF – Air sensor plus floor sensor: Regulation is based on  SET  POINT applied to the 
internal  room  temperature  sensor  but  also  controlled  by  the  floor  temperature  sensor 
ensuring that the floor temperature remains within the set limits. The lower floor temperature 
limit is specified in Param 15 - FtL and the high temperature limit in Param 16 – FtH.
3) F – Floor sensor: Regulation is based on the SET POINT applied to the external floor 
temperature sensor.
4) FA – Floor sensor plus air sensor: Regulation is based on SET POINT applied to the 
external floor sensor but is also controlled by the internal air temperature sensor ensuring 
that the room temperature remains within the set limits. The lower air temperature limit is 
specified in Param 13 - AtL and the higher temperature limit in Param 14 – AtH.
5) Power regulator: Regulation is based on the time settings for heating which will be ON 
during the time in Param 05 – POn and then OFF during the time in Param 06 - POf. This 
cycle will be repeated constantly.

Parameter 

Number

Default 

Value

Available 

Values

Display 

Indication

Description

01

dEg

Degree Mode

°C, °F

°C

02

In1

EXT input mode

0, 1, 2

1

03

In2

Mode number for EXT input action

1, 2, 3, 4, 5, 6

2

04

Sen

Source Sensor

A, AF, F, FA, 

P, PA, PF

F

05

Pon

Power Regulation ON time, min

10 - 90

15

06

POF

Power Regulation OFF time, min

10 - 90

15

07

dry

Dry Time, min

5 - 90

30

08

tCr

Time correction by controller

0, 1

1

09

tFo

Time format 

0, 1

0

10

dAy

Week Day

1 - 7

1

11

tIH

Time Hour

0 - 23

0

12

tIL

Time Minute

0 - 59

0

14

AtH

Air Temperature Maximum, °C / °F

5.0-37.0 in °C

41 - 99 in °F

27 / 81

13

AtL

Air Temperature Minimum, °C / °F

4.0-36.0 in °C

39 - 97 in °F

21 / 70

15

FtL

Floor Temperature Minimum, °C / °F

4.0-36.0 in °C

39 - 97 in °F

18 / 64

16

FtH

Floor Temperature Maximum, °C / °F

5.0-37.0 in °C

41 - 99 in °F

32 / 90

17

Fsr

Floor Sensor Resistance, kΩ

1 - 100

10

19

Ftc

Floor Temperature Calibration, °C / °F

-9.5-9.5 in °C
-17 - 17 in °F

0 / 0

18

Atc

Air Temperature Calibration, °C / °F

-9.5-9.5 in °C
-17 - 17 in °F

0 / 0

20

HYS

Temperature Hysteresis, °C / °F

0.1-9.5 in °C

0.1 - 17 in °F

0.5 / 

0.9

21

dIF

Temperature difference to send to 

controller, °C / °F

0.1-1.0 in °C

0.2 - 1.8 in °F

0.2 / 

0.3

22

brH

Active display brightness level 

1 - 4, but 

>=Param23

4

23

brL

Inactive display brightness level

1 - 4, but 

<=Param22

3

24

Abr

Auto LCD brightness control

0, 1

1

25

Ab1

Auto brightness level 1 max lumens

0 - 5000

30

26

Ab2

Auto brightness level 2 max lumens

0 - 5000

200

27

Ab3

Auto brightness level 3 max lumens

0 - 5000

3000

28

bSA

Basic Set Action

1, 2, 3, 4, 5, 6

6

29

nEt

Inclusion / Exclusion Mode

Inc, Ecl

Ecl

30

Prr

Power Meter total value & reset

0-999kwh

0