Parameter 19 (Ftc) – Floor Temperature Calibration
This parameter defines the offset value for floor temperature. Should the external floor
temperature sensor not be correctly calibrated then temperature changes are able to be
adjusted by up to +/- 9.5°C or +/- 17°F. This value will be added or subtracted from the floor
temperature sensor reading.
Factory default value is 0.
Parameter 20 (HYS) – HYSTERESIS (HYS)
The hysteresis value for temperature control. The thermostat will stabilize the temperature
with selected hysteresis. For example, if the SET POINT is set for 25°C and HYSTERESIS
is set for 0.5°C the thermostat will change the state to HEATING if the temperature will be
lower than 24.5°C and it will change the state to idle if temperature reaches 25.5°C.
The hysteresis can be changed from 0.1°C up to a maximum of 9.5°C in Celsius mode and
from 0.1°F to 17°F in Fahrenheit mode.
Factory default values are 0.5°C or 0.9°F.
Parameter 21 (dIF) – Temperature difference to send to controller
The thermostat will send a new temperature to the gateway only in case if the temperature
change is greater or equal than the value specified in this parameter.
From 0.1C to 1.0C can be chosen.
Factory default value is 0.2C
Note:
The thermostat is very sensitive to changes of ambient temperature and can often vary
by ±0.1C, therefore it is recommended to set this parameter from 0.2 and above to reduce the
load on your Z-Wave network.
DISPLAY BRIGHTNESS
The thermostat has two states of brightness.
Active state – when press any key and commence adjustments.
Inactive state – after five seconds of inactivity it will revert to inactive state.
The display brightness in either state can be adjusted.
Parameter 22 (brH) – Display brightness high level
The brightness level can be selected in the active state from values 1 (lowest brightness) to 4
(highest brightness) but the level cannot be lower than the level of brightness for the inactive
state (param 23).
Factory default value is 4.
Parameter 23 (brL) – Display brightness low level
This parameter defines the brightness level of the display in the inactive state. The level can
be selected from values 1 to 4 but the level cannot be higher than the level of brightness for
the active state (param 22).
Factory default value is 3.
Parameter 24 (Abr) – Auto brightness
The thermostat can adjust its display brightness automatically depending on the illumination
of the ambient environment. The comfort brightness of the screen can be chosen depending
on the room illumination in Parameters 25, 26 and 27.
Value 1 = Active the function, Value 0 = Inactive the function
Factory default value is 1.
Note:
The illumination of the environment can be checked at any time in the centre of the
display (on time position) in the device MENU on Parameter 24 or via your Z-Wave gateway
Parameter 25 (Ab1) – Auto brightness level 1 max lumens
The value indicates the maximum level of ambient illumination during which the brightness of
the display will be at level 1 (at the lowest level). For example if this parameter value is set 30
and the ambient illumination is in range 0-30 the display will be in lowest brightness level. As
soon as the illumination will be 31 or higher the display brightness will be changed to Level 2.
Factory default value is 30.
Parameter 26 (Ab2) – Auto brightness level 2 max lumens
This parameter indicate the maximum illumination for display brightness level 2. In case if the
illumination is in range Parameter 25 (Ab1) - Parameter 26 (Ab2) the display brightness will
be on level 2. If the illumination drops below the value of parameter 25 the brightness of the
display will be decreases to level 1, and if the illumination increases beyond the value of
parameter 26 the display brightness will rise to level 3.
Factory default value is 200.
Parameter 27 (Ab3) – Auto brightness level 3 max lumens
This parameter indicate the maximum illumination for display brightness level 3. In case if
ambient illumination raise above this value the display brightness will be changed to Level 4
Factory default value is 3000.
Parameter 28 (bsA) – Basic Sat Action
This parameter defines to which mode the thermostat operating mode will be changed to if
the Basic Set command is received.
If the received value of the Basic Set command is 0 (OFF state) the thermostat will go to MAN
mode and switch off the heating element (IDLE mode).
If the received value of the Basic Set command is 1 or higher (ON state) the thermostat will
change its mode regarding the value defined in this parameter.
If the parameter value is 1 the thermostat will go to the COM operating mode, value 2 is for
the TIME mode, Value 3 is for the DRY mode, Value 4 is for the ECO mode, Value 5 is for the
VAC, Value 6 is for the MAN.
If the parameter value is 6 (change to manual mode) and the Basic Set value is 1 or higher
(ON) the thermostat will go to the MAN mode and switch ON the HEAT mode.
Factory default value is 6.
Parameter 29 (nEt) – INCLUSION / EXCLUSION MODE
If the thermostat is included in the z-wave network the antenna will be indicated in the main
display and Inc will be indicated in the Param value. If the thermostat is not included in the
network, no antenna will be indicated in the main display and the Param value will be ECL.
To include or exclude the thermostat into/from your home automation gateway, activate
inclusion or exclusion mode on your gateway then go to Param 29 in the device Menu and
press “+” key for inclusion and the “-” key for exclusion.
For more details go to point “Z-Wave Functions” – “Network“of this manual.
Parameter 30 (Prr) – Power Meter values & reset
The Heltun thermostat monitors the load and total power consumption. The current load is
indicated in this Param values in the center of display (time position) in W. The data of total
consumption in kWh is indicated in the top right corner of the display.
If the device is included to the Z-Wave network it will also send the data of the current load
and total consumption to the main controller.
The thermostat, even when the electricity is disconnected, maintains the electric
consumption record in its memory.
To reset the consumption memory press and hold “+” key (about 3 seconds) until the
parameter total consumption value will be changed to 0.
Z-WAVE DEVICE TYPE:
GENERIC_TYPE_THERMOSTAT
SPECIFIC_TYPE_SETPOINT_THERMOSTAT
Supported Command Classes:
COMMAND_CLASS_BASIC,
COMMAND_CLASS_THERMOSTAT_OPERATING_STATE,
COMMAND_CLASS_THERMOSTAT_MODE,
COMMAND_CLASS_THERMOSTAT_SETPOINT,
COMMAND_CLASS_SENSOR_MULTILEVEL,
COMMAND_CLASS_METER,
COMMAND_CLASS_CLOCK,
COMMAND_CLASS_ZWAVEPLUS_INFO,
COMMAND_CLASS_TRANSPORT_SERVICE,
COMMAND_CLASS_SECURITY,
COMMAND_CLASS_SECURITY_2,
COMMAND_CLASS_VERSION,
COMMAND_CLASS_ASSOCIATION,
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION,
COMMAND_CLASS_ASSOCIATION_GRP_INFO,
COMMAND_CLASS_MANUFACTURER_SPECIFIC
,
COMMAND_CLASS_DEVICE_RESET_LOCALLY,
COMMAND_CLASS_POWERLEVEL,
COMMAND_CLASS_SUPERVISION,
COMMAND_CLASS_CONFIGURATION,
COMMAND_CLASS_FIRMWARE_UPDATE_MD
THERMOSTAT SETTINGS USING Z-WAVE PROTOCOL (GATEWAY)
All configuration parameters are accessed through
COMMAND_CLASS_CONFIGURATION
6) PA – Power reg Air sensor: Regulation is based on the time set by Params 05 and
06 but also controlled by the internal air temperature sensor ensuring that the room
temperature remains within the set limits. The air temperature limits are specified in Params
13 and 14.
7) PF – Power reg Floor sensor parameters: Regulation is based on the time set by
Params 05 and 06 but also controlled by the floor temperature sensor ensuring that the floor
temperature remains within the set limits. The floor temperature limits are specified in
Params 15 and 16.
For example:
In FA mode the SET POINT is set to 30°C, AtL is set to 24°C and AtH is set to 27°C:
a) If floor temperature is lower than 30°C and the room temperature is lower than 27°C the
thermostat will operate in HEATING mode.
b) If the floor temperature is higher than 30°C or the room temperature is higher than 27°C
then the thermostat will go to IDLE mode which switches off the heater.
c) If the room temperature is lower than 24°C the thermostat will operate in HEATING mode
even though the floor temperature is higher than 30°C.
Attention:
Be careful when setting the lower limitation (Param 13 - AtL and Param 15 – FtL)
to be sure that the value is not too high and it can be reached. Otherwise the thermostat will
always operate in the HEATING mode.
Note:
For safety reasons the thermostat will go to the IDLE mode if the floor temperature
reaches 40°C despite the parameter settings.
Note:
If there is no floor sensor installed or it becomes damaged (indicated by ” – “ in the
“FLOOR TEMP”) the regulation mode (A) will be automatically selected as the source
sensor. This can only be changed to (P) or (PA). Regulation modes (F), (FA), (AF) and (PF)
will not be able to be selected.
Factory default value is F.
Parameter 05 (POn) – Power regulation ON time
This parameter defines floor HEATING time in minutes when Power Regulator (P, PA or PF)
is selected as the source sensor in Param 04. Time can be changed in range 10 – 90 minutes.
Factory default value is 15 minutes.
Parameter 06 (POf) – Power regulation OFF time
Floor IDLE time in minutes when Power Regulator (P, PA or PF) is selected as the source
sensor. Time can be changed in range 10 – 90 minutes.
Factory default value is 15 minutes.
Parameter 07 (dry) – Dry Time
This parameter specifies how long in minutes the thermostat will be in HEATING mode when
the DRY mode is selected. After this time the thermostat will go to the TIME mode. The time
range is 5-90 minutes.
Factory default time is 30 minutes.
Parameter 08 (tCr) – Time correction by main controller
If this parameter value is 1 and the thermostat is connected to Z-Wave gateway the
thermostat time and weekday will be periodically polled and corrected from the gateway. To
switch off the auto correction set the parameter value 0.
Factory default value is 1.
Parameter 09 (tfo) – Time format
24-hours or 12-hours time indication format can be chosen.
0 = 24 hours format. 1 = 12 hours (AM/PM) format
Factory default value is 0.
Parameter 10 (day) – Week day
This parameter allows manually adjustment of the day of the week in case the thermostat is
not connected to any gateway or Parameter 08 (auto correction) selected as 0.
Parameter 11 (tIH) – Hour
This parameter allows manual adjustment of the hours.
Parameter 12 (tIL) – Minute
This parameter allows manual adjustment of the minutes.
Parameter 13 (AtL) – Air Temperature Minimum (Lowest level)
Room temperature low limit. Reading of internal temperature sensor. It has effect only if FA or
PA is selected as the source sensor in Param 04
Factory default value is 21°C or 70°F.
Note:
AtL value cannot be higher than AtH value - 1°C
Parameter 14 (AtH) – Air Temperature Maximum (Highest level)
Room temperature high limit. Reading of the internal temperature sensor. It has effect only if
FA or PA is selected as the source sensor.
Factory default value is 27°C or 81°F.
Note:
AtH value cannot be lower than AtL value + 1°C
Parameter 15 (FtL) – Floor Temperature Minimum (Lowest level)
Floor temperature low limit. Reading of external NTC temperature sensor. It has effect only if
AF or PF are selected as the source sensor.
Factory default value is 18°C or 64°F.
Note:
FtL value cannot be higher than FtH value - 1°C
Parameter 16 (FtH) – Floor Temperature Maximum (Highest level)
Floor temperature high limit. Reading of the external NTC temperature sensor. It has effect
only if AF or PF are selected as the source sensor.
Factory default value is 32°C or 90°F.
Note:
FtH value cannot be lower than FtL value + 1°C
Parameter 17 (FSr) – Floor sensor resistance
If the external floor NTC temperature sensor is used it is necessary to select the correct ohm
value (resistance) of the sensor. 1 – 100 kΩ is available to select. In the box is included one
floor NTC 10kΩ temperature sensor with a three metre connection wire.
Factory default value is 10kΩ.
Note:
If the floor sensor is disconnected or damaged “–” will indicate on the display FLOOR
TEMP field.
Parameter 18 (Atc) – Room Air Temperature Calibration
This parameter defines the offset value for room air temperature. If the internal air
temperature sensor is not correctly calibrated changes of temperature can be made by
adjusting the values by up to +/- 9.5°C or +/- 17°F. This value will be added or subtracted from
the internal air temperature sensor reading.
Factory default value is 0
Security:
S0, S2 unauthorized and S2 authorized inclusion modes are supported. If you use
S2 authorized inclusion mode the security key should be used in inclusion process.
NOTE:
Be sure to save this key. Without the key it is impossible to perform an inclusion in S2
authorized mode.
Exclusion
To exclude the thermostat from the Z-Wave network
1. Go to “SETTINGS” mode by pressing and holding the key for 3 seconds
2. Go to “Parameter 29 – nEt” of the menu
3. In the value position the current state of network state will be displayed. It should be “Inc”. if
the “ECL” is indicated the device is already excluded.
4. Start the exclusion from the gateway.
5. Press the “–” key to start the exclusion process
6. Lines will be moving in the value position.
7. The “Ecl” should appear with successful deletion.
8. If the “Err” appear then start the exclusion process again.
If the thermostat is included in the network, in the bottom right corner of the main screen the
antenna icon will be displayed with connection lines . If not on the network it will be
displayed without lines .
Association
Association enables the thermostat to control other Z-Wave products from the network.
Up to ten other products from different manufacturers can be within the association grouping.
The thermostat has two association groups:
Group 1 is for Life Line and used to connect Z-Wave gateway.
Through Group 2 the thermostat sends Basic Set command. It sends Basic Set command
with value 0 (Off state) when thermostat goes to IDLE mode and sends 255 (ON state) when
the thermostat goes to HEATING mode.
CHILD LOCK – LOC
To activate the child lock mode, press and hold the key till the icon will be indicated in
the bottom center of the display (about 5 seconds). To deactivate the child lock press the key
dddd
until the icon disappears.
FACTORY RESET – RES
By pressing and holding the “MODE” key for 6 seconds, the thermostat will enter the Factory
Reset mode and “Res” will appear in left bottom corner, “y” in top left corner and “n” in top right
corner. Press “+” key if reversion to factory reset is required or the key to cancel. The
factory reset will change all the parameters to the original factory defaults and will also
exclude from the Z-Wave network.
Z-WAVE NETWORK
Inclusion
To include the thermostat in the Z-Wave network
1. Go to the “SETTINGS” mode by pressing and holding the key for 3 seconds
2. Go to “Parameter 29 – nEt” of the menu by using the key for scrolling up and the
“MODE” key for scrolling down in parameters.
3. In the value position will be seen the current state of the network. It should be ECL. If Inc is
indicated, anexclusion must be first performed.
4. Start the inclusion mode from the gateway
5. Press “+” key to start inclusion process
6. Lines will be moving in value position.
7. The “Inc” should appear in the value position if the inclusion has been successful. The “Err”
will appear if the inclusion was not completed.
Note:
In case the device has been part of the Z-Wave network before and not excluded
since, inclusion is not possible. In this case, exclusion must be performed before inclusion.
If the thermostat is included in the network, in the bottom right corner of the main screen the
antenna icon will be displayed with connection lines . If not on the network then it will be
displayed without lines .
2-YEAR LIMITED WARRANTY
Heltun warrants this product to be free from defects in the workmanship or materials, under
normal use and service, for a period of two (2) years from the date of purchase by the
consumer. If at any time during the warranty period the product is determined to be defective
or malfunctions, Heltun shall repair or replace it (at Heltun's option).
If the product is defective,
(i) return it, with a bill of sale or other dated proof of purchase, to the place from which you
purchased it; or
(ii) contact Heltun Customer Care at [email protected]. Customer Care will make the
determination whether the product should be returned or whether a replacement product can
be sent to you.
THIS WARRANTY DOES NOT COVER REMOVAL OR REINSATLLATION COSTS.
THIS WARRANTY SHALL NOT APPLY IF IT IS SHOWN BY HELTUN THAT THE
DEFECT OR MALFUNCTION WAS CAUSED BY DAMAGE WHICH OCCURRED
WHILE THE PRODUCT WAS IN THE POSSESSION OF A CONSUMER THIS
WARRANTY SHALL NOT OBLIGATE HELTUN FOR ANY LABOR COSTS AND SHALL
NOT APPLY TO DEFECTS IN WORKMANSHIP OR MATERIALS FURNISHED BY
YOUR INSTALLER AS CONTRASTED TO DEFECTS IN THE THERMOSTAT ITSELF.
IMPLIED WARRANTIES OF MERCHANTABILITY OF FITNESS FOR A PARTICULAR
PURPOSE SHALL BE LIMITED IN DURATION TO THE AFORESAID TWO YEAR
P E R I O D. H E LT U N'S L I A B I L I T Y F O R I N C I D E N TA L O R C O N S E Q U E N T I A L
DAMAGES, OTHER THAN DAMAGES FOR PERSONAL INJURIES, RESULTING
FROM ANY BREACH OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE
LIMITED WARRANTY IS EXPRESSLY EXCLUDED. THIS LIMITED WARRANTY IS
VOID IF DEFECT(S) RESULT FROM FAILURE TO HAVE THIS THERMOSTAT
INSTALLED BY A QUALIFIED HEATING AND AIR CONDITIONING CONTRACTOR. IF
THE LIMITED WARRANTY IS VOID DUE TO FAILURE TO USE A QUALIFIED
CONTRACTOR, ALL DISCLAIMERS OF IMPLIED WARRANTIES SHALL BE
EFFECTIVE UPON INSTALLATION.
HELTUN SOLUTIONS LLC
82-84 ARAM STR. #46, 0002, YEREVAN, ARMENIA
WWW.HELTUN.COM [email protected]
Parameter
Number
Default
Value
Available
Values
Parameter
Size
Description
01
1 byte
Degree Mode
°C, °F
0
02
1 byte
EXT input mode
0, 1, 2
1
03
1 byte
Mode number for EXT input action
1, 2, 3, 4, 5, 6
2
04
1 byte
Source Sensor: 1=A, 2=AF, 3=F, 4=FA,
5=P, 6=PA, 7=PF
1, 2, 3, 4, 5,
6, 7
3
05
1 byte
Power Regulation ON time, min
10 - 90
15
06
1 byte
Power Regulation OFF time, min
10 - 90
15
07
1 byte
Dry Time, min
5 - 90
30
08
1 byte
Time correction by controller
0, 1
1
09
1 byte
Time format
0, 1
0
10
1 byte
Week Day
1 - 7
1
11
1 byte
Time Hour
0 - 23
0
12
1 byte
Time Minute
0 - 59
0
14
2 bytes
Air Temperature Maximum in °C, x10
50 - 370
270
13
2 bytes
Air Temperature Minimum in °C,
value X 10, e.g. 22.5°C=225
40 - 360
210
15
2 bytes
Floor Temperature Minimum in °C, x10
40 - 360
180
16
2 bytes
Floor Temperature Maximum in °C, x10
50 - 370
320
17
1 byte
Floor Sensor Resistance, kΩ
1 - 100
10
19
1 byte
Floor Temperature Calibration in °C, x10
-95 - 95
0
18
1 byte
Air Temperature Calibration in °C, x10
-95 - 95
0
20
1 byte
Temperature Hysteresis in °C, x10
1 - 95
5
21
1 byte
Temperature difference to send to
controller, value X 10
1 -10
2
22
1 byte
Active display brightness level
1 - 4, but
>=Param23
4
23
1 byte
Inactive display brightness level
1 - 4, but
<=Param22
3
24
1 byte
Auto LCD brightness control
0, 1
1
25
2 bytes
Auto brightness level 1 max lumens
0 - 5000
30
26
2 bytes
Auto brightness level 2 max lumens
0 - 5000
200
27
2 bytes
Auto brightness level 3 max lumens
0 - 5000
3000
28
1 byte
Basic Set Action
1, 2, 3, 4, 5, 6
6
29-50
Reserved by manufacturer
51
1 byte
Touch buttons sensitivity. 20=Supper
sensitive. 70=lowest sensitivity.
20 - 70
50
52
2 bytes
Morning start time. Format: HHMM.
e.g.08:00 should be sent as 0800
0000 - 2359
0600
53
2 bytes
Day start time. Format: HHMM.
0000 - 2359
0900
55
2 bytes
Night start time. Format: HHMM.
0000 - 2359
2300
54
2 bytes
Evening start time. Format: HHMM.
0000 - 2359
1800
56
2 bytes
Monday Morning temperature, valueX10
40 - 370
240
57
2 bytes
Monday Day temperature, valueX10
40 - 370
200
58
2 bytes
Monday Evening temperature, valueX10
40 - 370
230
59
2 bytes
Monday Night temperature, valueX10
40 - 370
180
60 - 63
2 bytes
Tuesday schedule temperatures:
P60=morning t°C, P61=day t°C,
P62=evening t°C, P63=night t°C
40 - 370
64 - 67
2 bytes
Wednesday schedule temperatures
40 - 370
68 - 71
2 bytes
Thursday schedule temperatures
40 - 370
72 - 75
2 bytes
Friday schedule temperatures
40 - 370
76 - 79
2 bytes
Saturday schedule temperatures
40 - 370
80 - 83
2 bytes
Sunday schedule temperatures
40 - 370